4 Mounting
OPTISOUND 3010 C • Four-wire 4 … 20 mA/HART
30504-EN-220310
max.
min.
1
Fig. 14: Standpipe in the tank
1 Vent hole: ø 5 … 10 mm (0.197 … 0.394 in)
OPTISOUND 3010 C can be used from tube diameters of 40 mm
(1.575 in).
Avoid large gaps and thick welding joints when connecting the tubes.
Generally carry out a false signal suppression.
Measurement in a standpipe is not recommended for extremely
adhesive products.
The short examples give you introductory information on flow
measurement. Detailed planning information is available from flume
manufacturers and in special literature.
3 ... 4 h
max
≥ 50 mm
90°
2
3
1
h
ma
x
d
mi
n
≥ 2 mm x
h
ma
x
90°
4
2
3
Fig. 15: Flow measurement with rectangular overfall: d
min.
= blocking distance of
the sensor (see chapter " Technical data"); h
max.
= max. filling of the rectangular
spillway
1 Overfall orifice (side view)
2 Upstream water
3 Tailwater
4 Overfall orifice (view from tailwater)
In general, the following points must be observed:
Flow measurement with
rectangular overfall