13
4 Mounting
OPTISOUND 3010 C • Four-wire 4 … 20 mA/HART
30504-EN-220310
Fig. 6: Vessel with conical bottom
Socket pieces should be dimensioned so that the lower end of the
transducer protrudes at least 10 mm (0.394 in) out of the nozzle.
~ 10 mm
Fig. 7: Recommended socket mounting
If the reflective properties of the medium are good, you can mount
OPTISOUND 3010 C on sockets which are higher than the length of
the transducer. You will find recommended values for socket heights in
the following illustration. The socket end should be smooth and burr-
free, if possible also rounded. Carry out a false signal suppression.