6.7 Voltage and frequency
Range (V)
Resolution (V)
Accuracy
0
÷
550
1
±(2 % of r 2 digits)
Frequency range 0 Hz, 45 Hz
÷
400 Hz
Range (Hz)
Resolution (Hz)
Accuracy
10
÷
499
0.1
±2 digits
Nominal voltage range
V
÷
550 V
6.8 Earth Resistance
Measuring range according to EN61557-5 is EN61557-5 es 1Ohm
÷
1999 Ω.
Re – Earth resistance, 3-wire, 4-wire
Range (Ω)
Resolution (Ω)
Accuracy*
1
÷
9999
(1.00 ... 19.99)
0.01
(20.0 ... 199.9)
0.1
(200.0 ... 9999)
1
±(5 % of r 5 digits)
Max. auxiliary earth electrode resistance Rh
100xRE or 50 kΩ (whichever is lower)
Max. probe resistance Rs
100xRE or 50 kΩ (whichever is lower)
Rh and Rs values are indicative.
Additional probe resistance error at Rhmax or Rsmax
±(10 % of r 10 digits)
Additional error at 3 V voltage noise (50 Hz)
±(5 % of r 10 digits)
Open circuit voltage
< 30 VAC
Short circuit current
< 30 mA
Test voltage frequency
126.9 Hz
Test voltage shape
sine wave
Automatic measurement of auxiliary electrode resistance and probe resistance.
Ro - Specific earth resistance
Range
Resolution (Ωm)
Accuracy
6.0 Ωm … 99.9 Ωm
0.1 Ωm
± (5 % of r 5 digits)
100 Ωm ... 999 Ωm
1 Ωm
± (5 % of r 5 digits)
1.00 kΩm ... 9.99 kΩm
0.01 kΩm
±(10% de lect.) for Re 2kΩ…19.99kΩ
10.0 kΩm ... 99.9 kΩm
0.1 kΩm
±(10% de lect.) for Re 2kΩ…19.99kΩ
100 kΩm ... 9999 kΩm
1 kΩm
±(20% de lect.) for Re > 20 kΩ