Multicheck6010
EN
- 83 -
Figure 4 38: Example of resistance to earth measurement results
Displayed results:
Re
Resistance to earth
Rs
Resistance of S (potential) probe
Rh
Resistance of H (current) probe
Notes:
•
If a voltage of higher than 10 V exists between test terminals, the Earth Resistance
measurement will not be performed.
4.8.2 Specific earth resistance (Ro)
How to perform Specific Earth Resistance measurement
Step 1
Select the
Earth Resistance
function with the function selector FCT key and select the
Ro
mode with the
▲▼
and
◀▶
navigation keys. The following menu will be displayed:
Figure 4 39: Specific Earth Resistance (Ro) measurement menu
Step 2
Set the following limit value:
•
Distance
: set distance “a” between test rods using the
▲▼
and
◀▶
navigation keys.
Step 3
Follow the connection diagram shown in figures 4.40 to perform the
Specific Earth
Resistance
measurement.