Multicheck6010
EN
- 88 -
RCD test current selection (r.m.s. value calculated to 20 ms) according to IEC 61009:
½xIΔN
1xIΔN
2xIΔN
5xIΔN
RCD IΔ
IΔN (mA)
AC
A
B
AC
A
B
AC
A
B
AC
A
B
AC
A
B
10
5
3,5
5
10
20
20
20
40
40
50
100 100
30
15
10,5
15
30
42
60
60
84
120 150 212 300
100
50
35
50
100 141 200 200 282 400 500 707 1000
300
150 105 150 300 424 600 600 848
*)
1500
*)
*)
500
250 175 250 500 707 1000 1000 1410
*)
2500
*)
*)
650
325 228 325 650 919 1300 1300
*)
*)
*)
*)
*)
1000
500 350 500 1000 1410
*)
2000
*)
*)
*)
*)
*)
*) not available
6.3.2 Contact voltage
Measuring range according to EN61557-6 is 3.0 V
÷
49.0 V for limit contact voltage 25 V.
Measuring range according to EN61557-6 is 3.0 V
÷
99.0 V for limit contact voltage 50 V.
Range (V)
Resolution (V)
Accuracy
3.0
÷
9.9
0.1
(-0 % / +10 %) of r 5 digits
10.0
÷
99.9
0.1
(-0%/+10%) of reading
Test current
0.5xIΔN
Limit contact voltage
25 V, 50 V
6.3.3 Trip-out time
Complete measurement range corresponds to EN61557-6 requirements. Specified accuracies
are valid for complete operating range.
Range (ms)
Resolution (ms)
Accuracy
0.0
÷
500.0
0.1
±3 ms
Test current
½xIΔN, IΔN, 2xIΔN, 5xIΔN
Multipliers not available see test current selection table
6.3.4 Trip-out current
Measurement range corresponds to EN61557-6 requirements. Specified accuracies are valid for
complete operating range.
Range I
Δ
Resolution I
Δ
Accuracy
0.2xIΔN
÷
1.1xIΔN (AC type)
0.05xIΔN
±0.1xIΔN
0.2xIΔN
÷
1.5xIΔN (A type, IΔN≥30 mA)
0.05xIΔN
±0.1xIΔN
0.2xIΔN
÷
2.2xIΔN (A type,IΔN=10 mA)
0.05xIΔN
±0.1xIΔN
0.2xIΔN
÷
2.2IΔN (B type)
0.05xIΔN
±0.1xIΔN