- 71 -
4.3.3 Trip-out current
How to perform trip-out current measurement
Step 1
Select the
RCD
function FCT key and select the
Ramp
mode with the
▲▼
and
◀▶
navigation keys. The following menu will be displayed:
Figure 4 16: Trip-out current measurement menu
Step 2
By using cursor keys the following parameters can be set in this measurement:
•
I
ΔN
: Nominal residual current
•
Type
: RCD type
•
Pol.
: Test current starting polarity
Step 3
Connect the test leads to the instrument and follow the connection diagram shown in
figure 4.12 (see the chapter 4.3.1 Contact voltage) to perform trip- out current
measurements.
Step 4
Check for any warnings and check the online voltage/terminal monitor on the display
before starting the measurement. If everything is ok and the is shown, press the
TEST key. After performing the measurement, the results appear on the display
together with the
or indication.
Figure 4 17: Example of trip-out current measurement result