Ducts connecting the unit to the exterior of the building must be insulated (insulation thickness
50–100 mm) to prevent condensation on cold surfaces.
•
Air intake and exhaust ducts must be fitted with air closing dampers (mechanical spring-loaded
or electric with actuators) to protect the unit from exposure to climatic conditions when the unit
is switched off.
•
In order to minimise AHU noise transferring through the ducts into ventilated areas, sound
attenuators must be connected to the unit.
•
Duct system elements must have separate brackets and to be mounted in a way that their weight
is not shifted to the unit casing.
•
Do not drill or screw self-tapping screws into the housing in other than specified locations as it
may damage internal wires and tubes.
The diameter of the ducts varies by unit model:
Unit
Duct diameter, mm
Duct A
Duct B
Duct C
Duct D
RHP
400 V
160
160
160
160
600 U
200
200
200
200
800 U
250
250
250
250
1300 U
250
250
250
250
1500 U
250
250
250
250