3.2. Inspection Area
Based on its type, an air handling unit may be installed indoors or outdoors. When selecting an installation or mounting
location, you must foresee sufficient and security compliant access space for repair and maintenance operations. The unit
must be installed in a way to allow partial or full disassembly and removal of assemblies out of the sections, if needed (e.g.,
in case of complex repairs).
B
C
≥500
A
≥B
Fig. 8.
Device inspection area
Minimum service area A defines an area which must be free of any stand-alone or immovable devices, equipment, parti-
tions, structure or furniture. This area is sufficient for performing service and filter replacement works. For repair and replace-
ment of components (e.g., removal of rotary heat exchangers), access area equal or wider to the width of the device B shall be
ensured in front of the device. Please note that the back wall of units must be removed for any repair works of the heat pump,
therefore, the distance between the mounted unit and the wall must be equal to or greater than the distance C. This gap will
also help to reduce transfer of noise and vibrations from the unit to walls, prevent moisture and mould due to condensation.
Unit model
A, mm
B, mm
C, mm
RHP
400 V
620
620
400
600 U
470
650
400
800 U
550
905
400
1300 U
550
905
400
1500 U
550
905
400
•
When selecting an installation or mounting location, keep in mind that preventive maintenance
works must be performed at least twice a year or more often, therefore, a safe and easy access to
the unit must be foreseen.