4
TS_622_02 PowerWAVE 9500DPA User Manual 26/2/19
2.2
Model range
As described previously, the PowerWAVE 9500DPA UPS cabinet can house up to five 100 kW UPS modules, so each
cabinet can be rated up to 500 kW in 100 kW increments.
Figure 2.1 PowerWAVE 9500DPA System hardware
Each UPS module comprises two sub-modules; one is known as the ‘Active’ sub-module and the other as the ‘Passive’
sub-module. These are mounted in the UPS cabinet in pairs, with the Active sub-module located on top of the Passive
sub-module. The first module to be installed in the cabinet must be fitted to the bottom position with subsequent modules
fitted in the next lowest available slot. When it is installed in the cabinet, each module is assigned an ID number to allow it
to be identified by the system control logic for purposes such as monitoring and event logging. The modules fitted in the
first cabinet should be identified as illustrated in Figure 2.1. In a multi-cabinet installation, the modules in the second
cabinet are given an identity ‘06’ to ‘10’, those in the third cabinet are given ‘11’ to ‘15’, and so on.
The following table shows the static parameters for each configuration.
1 Module 2 Module 3 Module 4 Module 5 Module
System power rating (per cabinet) (kVA/kW)
100
200
300
400
500
Cabinet weight including modules (kg)
539
648
757
866
975
Cabinet weight without fitted modules (kg)
430
Cabinet dimensions (w x h x d) mm
1580 x 1975 x 940
Heat dissipation 100% linear load (W)
4500
9000
13500
18000
22500
Heat dissipation 100% linear load (BTU)
15395
30717
46076
61434
76793
Heat dissipation 100% non-linear load (W)
5710
11420
17130
22840
28550
Heat dissipation 100% non-linear load (BTU)
19488
38976
58465
77953
97441
Heat dissipation no load (W))
660
1320
1980
2640
3300
Acoustic noise (@ 100% / 50% load)
75/67dBA (with 5 modules fitted)
Cooling airflow (25°C - 30°C) at full load (m³/s)
1200
2400
3600
4800
6000
Installation clearances (mm)
Front 1500, Side 100, Rear 200, Top 400
UPS Module weight
Active sub-module = 55 kg, Passive sub-module = 54 kg
UPS Module dimensions (w x h x d) mm
Active & Passive modules 710 x 178 x 750
RES E T
ON/OF F
ON/OF F
ENT E R
RES E T
ON/OF F
ON/OF F
ENT E R
RES E T
ON/OF F
ON/OF F
ENT E R
RES E T
ON/OF F
ON/OF F
ENT E R
RES E T
ON/OF F
ON/OF F
ENT E R
r ectifier
inver ter
load
dd.mm.yy
Load protected
P:01
hh:mm:ss
RES ET
ON/OF F
ON/OF F
ENT ER
Active sub-module
Passive sub-module
UPS Module 05
UPS Module 04
UPS Module 03
UPS Module 02
UPS Module 01
UPS Module
UPS Cabinet