background image

installation manual 

10

 
 
Bind  the  connecting  pipe  and  the  cables  together  tightly  with 
binding  tapes.Pass  the  bound  connecting  pipe  through  the 
wall conduct from outside. Be careful of the pipe allocation to 
do on damage to the tubing. 
  
Connect  the  pipes.  Refer  to  "How  to  Connect  the  pipes"  for 
details. 
 
Expel the air with a vacuum pump. Refer to "How to expel the 
air with a vacuum pump" for details. 
 
Open  the  stop  values  of  the  outdoor  unit  to  make  the 
refrigerant  pipe  connecting  the  indoor  unit  with  the  outdoor 
unit in fluent flow. 
 
Check the leakage. Check all the joints with the leak detector 
or soap water. 
 
Cover the joints of the connecting pipe with the soundproof / 
insulating  sheath  (fittings),  and  bind  it  well  with  the  tapes  to 
prevent leakage. 
 

Be sure to with insulating materials cover all the exposed 
parts  of  the  flare  pipe  joints  and  refrigerant  pipe  on  the 
liquid-side  and  the  gas-side.  Ensure  that  there  is  no  gap 
between them. 
Incomplete insulation may cause water condensation. 

CAUTION 

How to Connect the pipes 

Flaring 

Cut a pipe with a pipe cutter. 

(Refer to Fig.7-1) 

Insert a flare nut into a pipe and flare the pipe. 
 
Refer to Table 7-2 for the dimension of flare nut spaces. 

 Fig.7-1

90 

Lean     crude     burr 

Bend the tubing in proper way. Do not harm to them. 

Connect  the  indoor  unit  at  first,  then  the  outdoor 
unit. 

Too large torque will harm the bellmouthing and too small 
will  cause  leakage.  Please  determine  the  torque 
according to Table 7-2. 
After  the  connecting  work  is  finished,  be  sure  to  check 
that there is no gas leak. 
 

When connecting the flare nut, coat the flare both inside 
and outside with either oil or ester oil and initially tighten 
by hand 3 or 4 turns before tighting firmly. 

 

 

 

 

Be  sure  to  use  both  a  spanner  and  torque  wrench 
together when connecting or disconnecting pipes to /from 
the unit. 

 

Bend the pipe with thumb

min-radius 100mm

Fig.7-4

Fig.7-5

Fig.7-6

How to expel the air with a vacuum pump 

Stop valve operation introduction 

1.          Opening stop valve 

1. 

2. 

3. 

Remove  the  cap  and  turn  the  valve  counter 
clock-wise  with  the  hexagon  wrench. 

Turn it until the shaft stops.Do not apply excessive force 
to the stop valve. Doing so may break the valve body, 
as the valve is not a backseat type. Always use the 
special tool. 

Make sure to tighten the cap securely. 

CAUTION 

Table 7-2

Ø6.4 

8.3 

8.7 

Ø9.5 

12.0 

Ø12.7 

15.4 

Ø15.9 

Ø19.1 

18.6 

22.9 

R0.4~0.8 

45 ° 

± 2 

90 °      

± 4 

65

67N.m 

(663

684 kgf.cm) 

45

47 N.m 

(459

480 kgf.cm) 

35

36 N.m 

(357

367 kgf.cm) 

25

26N.m 

(255

265 kgf.cm) 

15

16 N.m 

(153

163 kgf.cm) 

(mm) 

min 

max 

Pipe  gauge 

Tightening     torque 

Flare dimensin A 

Flare     shape 

12.4 

15.8 

19.0 

23.3 

Remove  the  Cycle  Service  Panel  and  the  Cover 
Board, unscrewing the screws which secure it  to 
the structure 

Remove the protection cover of stop valve  

Fig.7-3

Liquid Valve

Gas Valve

The bending angle should not exceed 90. 

Bending  position  is  preferably  in  the  middle  of  the 
bendable pipe. The larger the bending radius the better it 
is. 

Do not bend the pipe more than three times. 

Fig.7-2

Cycle Service Panel

Cover Board

Summary of Contents for KUIM 012

Page 1: ...ng And Floor Type Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference INSTALLATION MANUAL KUIM 012 018 ...

Page 2: ...If used as MULTI unit please refer to the Installation operation manuals packed with outdoor unit ...

Page 3: ...ection of the fluid flow For electrical work follow the local national wiring standard regulation and this installation instructions An independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect in electrical work it will cause electrical shock fire Use the specified cable and connect tightly and clamp the cable so that no external force will be acted...

Page 4: ...lations Do not operate your air conditioner in a wet room such as a bathroom or laundry room There is petrolatum existing There is salty air surrounding near the coast There is caustic gas the sulfide for example existing in the air near a hot spring The Volt vibrates violently in the factories In buses or cabinets In kitchen where it is full of oil gas There is strong electromagnetic wave existin...

Page 5: ...ion The indoor unit should be installed in a location that meets the following requirements CAUTION Fig 5 1 35mm 1000mm 35mm 35mm QUANTITY SHAPE NAME 1 Hook 7 Owner s manual 8 Installation manual 9 Remote controller manual 3 Remote controller 4 Remote controller holder 6 Alkaline dry batteries AM4 2 Hanging arm 2 2 2 1 1 Installation fittings Remote controller Its Holder Others 5 Mounting screw ST...

Page 6: ... handling to the ceiling varies from the constructions consult the construction person for the specific condition Do keep the ceiling flat Consolidate the roof beam to avoid 1 Installing Ø10 hanging screw bolts 4 bolts possible vibration After the selection of installation location position the refrigerant pipes drain pipes indoor outdoor wires to the connection places before hanging up the machin...

Page 7: ...ld be installed in the location that meets the following requiements Mounting bolt max 40mm Fig 5 13 8 13mm INDOOR UNIT unit mm Fig 5 15 Fig 5 16 D Connecting point of refrigerant pipe D gas side Drain point E Connecting point of refrigerant pipe E Liquid side G C Fig 5 17 There is enough room for installation and maintenance The air outlet and the air inlet are not impeded and can not be reached ...

Page 8: ...e outdoor unit The condensate should be well drained away by the drain hole to an appropriate place so as not to interfere other people Select the position where it will not be subject to snow drifts accumulation of leaves or other seasonal debris If unavoidable please cover it with a shelter Locate the outdoor unit as close to the indoor unit as possible If possible please remove the obstacles ne...

Page 9: ...45 360 990 624 366 396 340 965 345 360 940 600 376 400 340 1245 360 940 590 378 400 330 1170 350 900 42 48 60 12 Fig 6 2 780 548 266 300 241 540 250 Fig 6 2 Fig 6 2 Fig 6 2 Fig 6 2 900 590 333 355 302 860 315 Fig 6 2 Fig 6 2 Fig 6 2 Fig 6 2 Fig 6 3 Fig 6 2 Fig 6 3 Fig 6 2 Fig 6 3 Fig 6 3 590 378 400 330 1170 350 900 Fig 6 3 634 404 448 368 1369 392 938 Fig 6 3 634 404 448 368 1369 392 938 Fig 6 3 ...

Page 10: ...psing in case of earthquake or strong wind Refer to Fig 6 15 NOTE NOTE Four different configuration are available for oudoor unit only changing the panels and fan position Keep in mind that fan unit weight is aprox 30Kg the unit as well as relevant equipment covered with the vinyl cover during installation work To change air inlet is only necessary to interchange the indicated panels position Both...

Page 11: ...ption Outdoor Unit Vibration proof rubber Anchor Bolt M10 Drainage Wide 100 Depth 150 Drainage Mortar Hole Φ100 Depth 150 Sling Bolt Suspension Bracket Table 6 4 Table 6 5 Fig 6 17 MODEL B C 1120 720 1328 740 1338 820 1338 820 18 24 30 36 30 36 48 60 1 2 3 4 5 Table 7 1 Drill a hole in the wall suitable just for the size of the wall conduit then set on the fittings such as the wall conduit and its...

Page 12: ...age Please determine the torque according to Table 7 2 After the connecting work is finished be sure to check that there is no gas leak When connecting the flare nut coat the flare both inside and outside with either oil or ester oil and initially tighten by hand 3 or 4 turns before tighting firmly Be sure to use both a spanner and torque wrench together when connecting or disconnecting pipes to f...

Page 13: ...m pump Open the Lo lever of the manifold value completely Turn on the vacuum pump At the beginning of pumping loosen the maintenance nut of stop valve B a little to check whether the air comes in the sound of the pump changes and the indicator of compound meter turns below zero Then fasten the maintenace nut When the pumping has finished close the Lo lever of the manifold valve completely and turn...

Page 14: ...s position is shown figure below Drain Piping Fig 8 2 Fit the seal into the drain joint then insert the drain joint into 0 the base pan hole of outdoor rotate 90 to securely assemble them Connect the drain joint with an extension drain hose Locally purchased in case of the condensate draining off the outdoor unit during the heating mode Refer to Fig 8 2 Plug 75 Slope 2 Prepare a polyviny chloride ...

Page 15: ...b Whether the generated wind noise or condensed of by the air conditioner have influenced your neighborhood c Whether any of the refrigerant is leaked A protection feature prevents the air conditioner from being activated for approximately 3 minutes when it is restarted immediately after shut off CAUTION 1 The indoor unit a Whether the switch on the remote controller works well b Whether the butto...

Page 16: ...V 1Phase 208 240V 1Phase MODEL POWER CIRCUIT BREAKER FUSE A PHASE FREQUENCY AND VOLT 30 36 30 36 42 60 42 60 380 420V 25 20 25 20 40 25 45 35 208 240V 3Phase 380 420V 3Phase 3Phase 208 240V 3Phase Table 9 3 Table 9 4 MODEL POWER CIRCUIT BREAKER FUSE A PHASE FREQUENCY AND VOLT 24 60 30 36 42 48 208 240V 1Phase 208 240V 1Phase 208 240V 1Phase 208 240V 1Phase MODEL POWER CIRCUIT BREAKER FUSE A PHASE ...

Page 17: ...30 36 30 36 42 60 42 60 380 420V 25 20 25 20 40 25 45 35 208 240V 3Phase 380 420V 3Phase 3Phase 208 240V 3Phase Table 9 5 Table 9 6 PHASE FREQUENCY AND VOLT POWER indoor POWER outdoor 30 20 30 20 40 30 40 35 50 40 208 240V 208 240V 1Phase 1Phase 208 240V 1Phase 208 240V 1Phase 208 240V 1Phase MODEL POWER indoor POWER outdoor POWER indoor POWER outdoor CIRCUIT BREAKER FUSE A CIRCUIT BREAKER FUSE A ...

Page 18: ...Outdoor Strong elec signal link wiring Weak elec signal link wiring Indoor Unit Outdoor Unit Ground the air conditioner properly in case to affect its anti interference function Ground wiring Ground wiring Power supply Switch Fuse Available locally Power wiring indoor Power linking wiring Outdoor Strong elec signal link wiring Weak elec signal link wiring Indoor Unit Outdoor Unit Ground the air co...

Page 19: ...ffect its anti interference function A disconnection device having an air gap contact separation in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation When wiring please choose the corresponding chart or it may cause damage The signs of the indoor terminal block in the some of following fugures may be replaced by L N L1 N1 Before obtaining ...

Page 20: ... are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Tel 305 594 4972 Fax 305 499 4378 www klimaire com sales klimaire com 2190 NW 89 Place Doral FL 33172 USA ...

Reviews: