background image

installation manual 

2

To install properly, please read this "installation manual" at 
first. 
 
The air conditioner must be installed by qualified persons. 
 
When installing the indoor unit or its tubing, please follow 
this manual as strictly as possible. 
 
If  the  air  conditioner  is  installed  on  a  metal  part  of  the 
building,  it  must  be  electrically  insulated  according  to  the 
relevant standards to electrical appliances.

 

 
When  all  the  installation  work  is  finished,  please  turn  on 
the power only after a thorough check. 
 
Regret for no further announcement if there is any change 
of this manual caused by product improvement. 

2.    INSTALLATION INFORMATION

Ground the air conditioner.

 

Do  not  connect  the  ground  wire  to  gas  or  water  pipes, 
lightning  rod  or  a  telephone  ground  wire.

Inappropriate

 

grounding may result in electric shocks. 
 

Be sure to install an earth leakage breaker.

 

Failure  to  install  an  earth  leakage  breaker  may  result  in 
electric shocks. 

 

Connect the outdoor unit wires , then connect the indoor 
unit wires.

  

You  are  not 

allowed

  to  connect  the  air  conditioner  with  the 

power supply until the wiring and piping is done

 
While  following  the  instructions  in  this  installation 
manual,  install  drain  piping  in  order  to  ensure  proper 
drainage  and  insulate  piping  in  order  to  prevent 
condensation.

 

Improper  drain  piping  may  result  in  water  leakage  and 
property damage. 
 

Install the indoor and outdoor units, power supply wiring 
and  connecting  wires 

  at  least  1  meter  away 

should  be

from  televisions  or 

radios  in  order  to  prevent  image 

interference or noise. 

Depending on the radio waves, a distance of 1 meter may not 
be sufficient enough to eliminate the noise. 

 
The appliance is not intended for use by young children 
or infirm persons without supervision. 

 

Don't  install  the  air  conditioner  in  the  following 

circumstance: 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The  appliance  shall  be  installed  in  accordance  with 
national wiring regulations. 
 
Do  not  operate  your  air  conditioner  in  a  wet  room  such 
as a bathroom or laundry room. 

There is petrolatum existing. 
 
There is salty air surrounding (near the coast). 
 
There is caustic gas (the sulfide, for example) existing  
in the air (near a hot spring). 
 
The Volt vibrates violently (in the factories). 
 
In buses or cabinets. 
 
In kitchen where it is full of oil gas. 
 
There is strong electromagnetic wave existing. 
 
There are inflammable materials or gas. 
 
There is acid or alkaline liquid evaporating. 
 
Other special conditions. 

If  the  refrigerant  leaks  during  installation,  ventilate  the 
area immediately. 

Toxic  gas  may  be  produced  if  the  refrigerant  comes  into  the 
place contacting with fire. 
 

The temperature of refrigerant circuit will be high, please 
keep  the  interconnection  cable  away  from  the  copper 
tube. 
 
After  completing  the  installation  work,  check  that  the 
refrigerant does not leak. 

Toxic  gas  may  be  produced  if  the  refrigerant  leaks  into  the 
room and comes into contact with a source of fire, such as a 
fan heater, stove or cooker. 

INSTALLATION ORDER 

Select the location; 
 
Install the indoor unit; 
 
Install the outdoor unit; 
 
Install the connecting pipe ; 
 
Connect the drain pipe; 
 
Wiring; 
 
Test operation. 

CAUTION 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

An all-pole disconnection device which has at least 3mm 
clearances  in  all  poles  ,  and  have  a  leakage  current  that 
may  exceed  10mA,  the  residual  current  device  (RCD) 
having  a  rated  residual  operating  current  not  exceeding 
30mA,  and  disconnection  must  be  incorporated  in  the 
fixed wiring in accordance with the wiring rules. 

3.   INSPECTING AND HANDLING THE UNIT

At delivery, the package should be checked and any damage should 
be reported immediately to the the service agent. 
 
When handling the unit, take into account the following: 

          Fr

agile, handle the unit with care. 

 
        Keep the unit upright in order to avoid compressor 
damage. 
 
Choose on before hand the path along which the unit is to be 
brought in. 
 
Move this unit as originally package as possible. 
 
When lifting the unit , always use protectors to prevent belt 
damage and pay attention to the position of the unit’s centre of 
gravity. 

 

Summary of Contents for KUIM 012

Page 1: ...ng And Floor Type Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference INSTALLATION MANUAL KUIM 012 018 ...

Page 2: ...If used as MULTI unit please refer to the Installation operation manuals packed with outdoor unit ...

Page 3: ...ection of the fluid flow For electrical work follow the local national wiring standard regulation and this installation instructions An independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect in electrical work it will cause electrical shock fire Use the specified cable and connect tightly and clamp the cable so that no external force will be acted...

Page 4: ...lations Do not operate your air conditioner in a wet room such as a bathroom or laundry room There is petrolatum existing There is salty air surrounding near the coast There is caustic gas the sulfide for example existing in the air near a hot spring The Volt vibrates violently in the factories In buses or cabinets In kitchen where it is full of oil gas There is strong electromagnetic wave existin...

Page 5: ...ion The indoor unit should be installed in a location that meets the following requirements CAUTION Fig 5 1 35mm 1000mm 35mm 35mm QUANTITY SHAPE NAME 1 Hook 7 Owner s manual 8 Installation manual 9 Remote controller manual 3 Remote controller 4 Remote controller holder 6 Alkaline dry batteries AM4 2 Hanging arm 2 2 2 1 1 Installation fittings Remote controller Its Holder Others 5 Mounting screw ST...

Page 6: ... handling to the ceiling varies from the constructions consult the construction person for the specific condition Do keep the ceiling flat Consolidate the roof beam to avoid 1 Installing Ø10 hanging screw bolts 4 bolts possible vibration After the selection of installation location position the refrigerant pipes drain pipes indoor outdoor wires to the connection places before hanging up the machin...

Page 7: ...ld be installed in the location that meets the following requiements Mounting bolt max 40mm Fig 5 13 8 13mm INDOOR UNIT unit mm Fig 5 15 Fig 5 16 D Connecting point of refrigerant pipe D gas side Drain point E Connecting point of refrigerant pipe E Liquid side G C Fig 5 17 There is enough room for installation and maintenance The air outlet and the air inlet are not impeded and can not be reached ...

Page 8: ...e outdoor unit The condensate should be well drained away by the drain hole to an appropriate place so as not to interfere other people Select the position where it will not be subject to snow drifts accumulation of leaves or other seasonal debris If unavoidable please cover it with a shelter Locate the outdoor unit as close to the indoor unit as possible If possible please remove the obstacles ne...

Page 9: ...45 360 990 624 366 396 340 965 345 360 940 600 376 400 340 1245 360 940 590 378 400 330 1170 350 900 42 48 60 12 Fig 6 2 780 548 266 300 241 540 250 Fig 6 2 Fig 6 2 Fig 6 2 Fig 6 2 900 590 333 355 302 860 315 Fig 6 2 Fig 6 2 Fig 6 2 Fig 6 2 Fig 6 3 Fig 6 2 Fig 6 3 Fig 6 2 Fig 6 3 Fig 6 3 590 378 400 330 1170 350 900 Fig 6 3 634 404 448 368 1369 392 938 Fig 6 3 634 404 448 368 1369 392 938 Fig 6 3 ...

Page 10: ...psing in case of earthquake or strong wind Refer to Fig 6 15 NOTE NOTE Four different configuration are available for oudoor unit only changing the panels and fan position Keep in mind that fan unit weight is aprox 30Kg the unit as well as relevant equipment covered with the vinyl cover during installation work To change air inlet is only necessary to interchange the indicated panels position Both...

Page 11: ...ption Outdoor Unit Vibration proof rubber Anchor Bolt M10 Drainage Wide 100 Depth 150 Drainage Mortar Hole Φ100 Depth 150 Sling Bolt Suspension Bracket Table 6 4 Table 6 5 Fig 6 17 MODEL B C 1120 720 1328 740 1338 820 1338 820 18 24 30 36 30 36 48 60 1 2 3 4 5 Table 7 1 Drill a hole in the wall suitable just for the size of the wall conduit then set on the fittings such as the wall conduit and its...

Page 12: ...age Please determine the torque according to Table 7 2 After the connecting work is finished be sure to check that there is no gas leak When connecting the flare nut coat the flare both inside and outside with either oil or ester oil and initially tighten by hand 3 or 4 turns before tighting firmly Be sure to use both a spanner and torque wrench together when connecting or disconnecting pipes to f...

Page 13: ...m pump Open the Lo lever of the manifold value completely Turn on the vacuum pump At the beginning of pumping loosen the maintenance nut of stop valve B a little to check whether the air comes in the sound of the pump changes and the indicator of compound meter turns below zero Then fasten the maintenace nut When the pumping has finished close the Lo lever of the manifold valve completely and turn...

Page 14: ...s position is shown figure below Drain Piping Fig 8 2 Fit the seal into the drain joint then insert the drain joint into 0 the base pan hole of outdoor rotate 90 to securely assemble them Connect the drain joint with an extension drain hose Locally purchased in case of the condensate draining off the outdoor unit during the heating mode Refer to Fig 8 2 Plug 75 Slope 2 Prepare a polyviny chloride ...

Page 15: ...b Whether the generated wind noise or condensed of by the air conditioner have influenced your neighborhood c Whether any of the refrigerant is leaked A protection feature prevents the air conditioner from being activated for approximately 3 minutes when it is restarted immediately after shut off CAUTION 1 The indoor unit a Whether the switch on the remote controller works well b Whether the butto...

Page 16: ...V 1Phase 208 240V 1Phase MODEL POWER CIRCUIT BREAKER FUSE A PHASE FREQUENCY AND VOLT 30 36 30 36 42 60 42 60 380 420V 25 20 25 20 40 25 45 35 208 240V 3Phase 380 420V 3Phase 3Phase 208 240V 3Phase Table 9 3 Table 9 4 MODEL POWER CIRCUIT BREAKER FUSE A PHASE FREQUENCY AND VOLT 24 60 30 36 42 48 208 240V 1Phase 208 240V 1Phase 208 240V 1Phase 208 240V 1Phase MODEL POWER CIRCUIT BREAKER FUSE A PHASE ...

Page 17: ...30 36 30 36 42 60 42 60 380 420V 25 20 25 20 40 25 45 35 208 240V 3Phase 380 420V 3Phase 3Phase 208 240V 3Phase Table 9 5 Table 9 6 PHASE FREQUENCY AND VOLT POWER indoor POWER outdoor 30 20 30 20 40 30 40 35 50 40 208 240V 208 240V 1Phase 1Phase 208 240V 1Phase 208 240V 1Phase 208 240V 1Phase MODEL POWER indoor POWER outdoor POWER indoor POWER outdoor CIRCUIT BREAKER FUSE A CIRCUIT BREAKER FUSE A ...

Page 18: ...Outdoor Strong elec signal link wiring Weak elec signal link wiring Indoor Unit Outdoor Unit Ground the air conditioner properly in case to affect its anti interference function Ground wiring Ground wiring Power supply Switch Fuse Available locally Power wiring indoor Power linking wiring Outdoor Strong elec signal link wiring Weak elec signal link wiring Indoor Unit Outdoor Unit Ground the air co...

Page 19: ...ffect its anti interference function A disconnection device having an air gap contact separation in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation When wiring please choose the corresponding chart or it may cause damage The signs of the indoor terminal block in the some of following fugures may be replaced by L N L1 N1 Before obtaining ...

Page 20: ... are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Tel 305 594 4972 Fax 305 499 4378 www klimaire com sales klimaire com 2190 NW 89 Place Doral FL 33172 USA ...

Reviews: