background image

installation manual 

13

Dissemble  the  bolts  from  the  cover.(If  there  isn't  a  cover  on 
the outdoor unit, disassemble the bolts from the maintenance 
board,  and  pull  it  in  the  direction  of  the  arrow  to  remove  the 
protection board.)  (Refer to 

Fig.9-1, Fig.9-2, Fig.9-3

Connect  the  connective  cables  to  the  terminals  as  identified 
with  their  respective  mached  numbers  on  the  terminal  block 
of indoor and outdoor units. 

Re-install the cover or the protection board. 

Connect the cable 

9.1 

The Specification of Power 

9.2 

Wiring figure 

9.3 

(Refer to Table9-1

Table 9-15) 

(Refer to Fig.9-4

Fig.9-36) 

Fig.9-1

Fig.9-2

Protection board

Cover

Protection Board

For  detailed  installation  acceptance  please  refer  to  your 
power  supplier,  if  restrictions  do  apply  for  products  like 
washing machines, air conditioners or electrical ovens. 

For power details of the air conditioner refer to the rating 
plate of the product. 

For any question contact your local dealer.

Remark per EMC Directive 2004/108/EC.
For  to  prevent  flicker  impressions  during  the  start  of  the 
compressor  (technical  process)  ,following  installation 
conditions do apply.

NOTE 

The  power  connection  for  the  air  conditioner  has  to  be 
done at the main power distribution. The distribution has 
to  be  of  a  low  impedance,  normally  the  required 
impedance reaches at a 32 A fusing point.

No other equipment has to be connected with this power 
line.

Split type outdoor unit

Vertical discharge type outdoor unit

All  the figures   in  this  manual  are  for  explanation 
purpose only. They may be slightly different from the air 
conditioner you purchased.The actual unit shall prevail. 

NOTE 

Fig.9-3

Protection Board

Centrifugal fan outdoor unit 

2) The outdoor unit 
a.  Whether  there  is  vibration  or  abnormal  noise  during 
operation. 
b. Whether the generated wind, noise, or condensed of by 
the air conditioner have influenced your neighborhood. 
c. Whether any of the refrigerant is leaked.  

A  protection  feature  prevents  the  air  conditioner  from  being 
activated  for  approximately  3  minutes  when  it  is  restarted 
immediately after shut off. 

CAUTION 

1) The indoor unit 
a. Whether the switch on the remote controller works well. 
b.  Whether  the  buttons  on  the  remote  controller  works 
well. 
c. Whether the air flow louver moves normally. 
d. Whether the room temperature is adjusted well. 
e. Whether the indicator lights normally. 
f. Whether the temporary buttons works well. 
g. Whether the drainage is normal. 
h.  Whether  there  is  vibration  or  abnormal  noise  during 
operation. 
I. Whether the air conditioner heats well in the case of the 
HEATING/COOLING type. 

Set  the  air  conditioner  under  the  mode  of  "COOLING"  with 
the remote controller, and check the following points. If there 
is any malfunction, please resolve it according to the chapter 
"Troubleshooting" in the "Owner's Manual".  

10.  TEST OPERATION

Test operation 

The  test  operation  must  be  carried  out  after  the  entire 
installation has been completed. 
 
Please confirm the following points before the test operation: 

According  to  the  user's  requirement,  install  the  remote 
controller  frame  where  the  remote  controller's  signal  can 
reach the indoor unit smoothly. 

The  power  voltage  fits  the  rated  voltage  of  the  air 
conditioner. 

There is no obstacle at the outlet and inlet of the outdoor 
and indoor units. 

The gas-side and liquid-side stop valves are both opened. 

The air conditioner is pre-heated by turning on the power. 

The indoor unit and outdoor unit are installed properly. 

Tubing and wiring are correctly completed. 

The refrigerant pipe system is leakage-checked. 

The drainage is unimpeded. 

The heating insulation works well. 

The ground wiring is connected correctly. 

The  length  of  the  tubing  and  the  added  stow  capacity  of 
the refrigerant have been recorded. 

Summary of Contents for KUIM 012

Page 1: ...ng And Floor Type Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference INSTALLATION MANUAL KUIM 012 018 ...

Page 2: ...If used as MULTI unit please refer to the Installation operation manuals packed with outdoor unit ...

Page 3: ...ection of the fluid flow For electrical work follow the local national wiring standard regulation and this installation instructions An independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect in electrical work it will cause electrical shock fire Use the specified cable and connect tightly and clamp the cable so that no external force will be acted...

Page 4: ...lations Do not operate your air conditioner in a wet room such as a bathroom or laundry room There is petrolatum existing There is salty air surrounding near the coast There is caustic gas the sulfide for example existing in the air near a hot spring The Volt vibrates violently in the factories In buses or cabinets In kitchen where it is full of oil gas There is strong electromagnetic wave existin...

Page 5: ...ion The indoor unit should be installed in a location that meets the following requirements CAUTION Fig 5 1 35mm 1000mm 35mm 35mm QUANTITY SHAPE NAME 1 Hook 7 Owner s manual 8 Installation manual 9 Remote controller manual 3 Remote controller 4 Remote controller holder 6 Alkaline dry batteries AM4 2 Hanging arm 2 2 2 1 1 Installation fittings Remote controller Its Holder Others 5 Mounting screw ST...

Page 6: ... handling to the ceiling varies from the constructions consult the construction person for the specific condition Do keep the ceiling flat Consolidate the roof beam to avoid 1 Installing Ø10 hanging screw bolts 4 bolts possible vibration After the selection of installation location position the refrigerant pipes drain pipes indoor outdoor wires to the connection places before hanging up the machin...

Page 7: ...ld be installed in the location that meets the following requiements Mounting bolt max 40mm Fig 5 13 8 13mm INDOOR UNIT unit mm Fig 5 15 Fig 5 16 D Connecting point of refrigerant pipe D gas side Drain point E Connecting point of refrigerant pipe E Liquid side G C Fig 5 17 There is enough room for installation and maintenance The air outlet and the air inlet are not impeded and can not be reached ...

Page 8: ...e outdoor unit The condensate should be well drained away by the drain hole to an appropriate place so as not to interfere other people Select the position where it will not be subject to snow drifts accumulation of leaves or other seasonal debris If unavoidable please cover it with a shelter Locate the outdoor unit as close to the indoor unit as possible If possible please remove the obstacles ne...

Page 9: ...45 360 990 624 366 396 340 965 345 360 940 600 376 400 340 1245 360 940 590 378 400 330 1170 350 900 42 48 60 12 Fig 6 2 780 548 266 300 241 540 250 Fig 6 2 Fig 6 2 Fig 6 2 Fig 6 2 900 590 333 355 302 860 315 Fig 6 2 Fig 6 2 Fig 6 2 Fig 6 2 Fig 6 3 Fig 6 2 Fig 6 3 Fig 6 2 Fig 6 3 Fig 6 3 590 378 400 330 1170 350 900 Fig 6 3 634 404 448 368 1369 392 938 Fig 6 3 634 404 448 368 1369 392 938 Fig 6 3 ...

Page 10: ...psing in case of earthquake or strong wind Refer to Fig 6 15 NOTE NOTE Four different configuration are available for oudoor unit only changing the panels and fan position Keep in mind that fan unit weight is aprox 30Kg the unit as well as relevant equipment covered with the vinyl cover during installation work To change air inlet is only necessary to interchange the indicated panels position Both...

Page 11: ...ption Outdoor Unit Vibration proof rubber Anchor Bolt M10 Drainage Wide 100 Depth 150 Drainage Mortar Hole Φ100 Depth 150 Sling Bolt Suspension Bracket Table 6 4 Table 6 5 Fig 6 17 MODEL B C 1120 720 1328 740 1338 820 1338 820 18 24 30 36 30 36 48 60 1 2 3 4 5 Table 7 1 Drill a hole in the wall suitable just for the size of the wall conduit then set on the fittings such as the wall conduit and its...

Page 12: ...age Please determine the torque according to Table 7 2 After the connecting work is finished be sure to check that there is no gas leak When connecting the flare nut coat the flare both inside and outside with either oil or ester oil and initially tighten by hand 3 or 4 turns before tighting firmly Be sure to use both a spanner and torque wrench together when connecting or disconnecting pipes to f...

Page 13: ...m pump Open the Lo lever of the manifold value completely Turn on the vacuum pump At the beginning of pumping loosen the maintenance nut of stop valve B a little to check whether the air comes in the sound of the pump changes and the indicator of compound meter turns below zero Then fasten the maintenace nut When the pumping has finished close the Lo lever of the manifold valve completely and turn...

Page 14: ...s position is shown figure below Drain Piping Fig 8 2 Fit the seal into the drain joint then insert the drain joint into 0 the base pan hole of outdoor rotate 90 to securely assemble them Connect the drain joint with an extension drain hose Locally purchased in case of the condensate draining off the outdoor unit during the heating mode Refer to Fig 8 2 Plug 75 Slope 2 Prepare a polyviny chloride ...

Page 15: ...b Whether the generated wind noise or condensed of by the air conditioner have influenced your neighborhood c Whether any of the refrigerant is leaked A protection feature prevents the air conditioner from being activated for approximately 3 minutes when it is restarted immediately after shut off CAUTION 1 The indoor unit a Whether the switch on the remote controller works well b Whether the butto...

Page 16: ...V 1Phase 208 240V 1Phase MODEL POWER CIRCUIT BREAKER FUSE A PHASE FREQUENCY AND VOLT 30 36 30 36 42 60 42 60 380 420V 25 20 25 20 40 25 45 35 208 240V 3Phase 380 420V 3Phase 3Phase 208 240V 3Phase Table 9 3 Table 9 4 MODEL POWER CIRCUIT BREAKER FUSE A PHASE FREQUENCY AND VOLT 24 60 30 36 42 48 208 240V 1Phase 208 240V 1Phase 208 240V 1Phase 208 240V 1Phase MODEL POWER CIRCUIT BREAKER FUSE A PHASE ...

Page 17: ...30 36 30 36 42 60 42 60 380 420V 25 20 25 20 40 25 45 35 208 240V 3Phase 380 420V 3Phase 3Phase 208 240V 3Phase Table 9 5 Table 9 6 PHASE FREQUENCY AND VOLT POWER indoor POWER outdoor 30 20 30 20 40 30 40 35 50 40 208 240V 208 240V 1Phase 1Phase 208 240V 1Phase 208 240V 1Phase 208 240V 1Phase MODEL POWER indoor POWER outdoor POWER indoor POWER outdoor CIRCUIT BREAKER FUSE A CIRCUIT BREAKER FUSE A ...

Page 18: ...Outdoor Strong elec signal link wiring Weak elec signal link wiring Indoor Unit Outdoor Unit Ground the air conditioner properly in case to affect its anti interference function Ground wiring Ground wiring Power supply Switch Fuse Available locally Power wiring indoor Power linking wiring Outdoor Strong elec signal link wiring Weak elec signal link wiring Indoor Unit Outdoor Unit Ground the air co...

Page 19: ...ffect its anti interference function A disconnection device having an air gap contact separation in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation When wiring please choose the corresponding chart or it may cause damage The signs of the indoor terminal block in the some of following fugures may be replaced by L N L1 N1 Before obtaining ...

Page 20: ... are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Tel 305 594 4972 Fax 305 499 4378 www klimaire com sales klimaire com 2190 NW 89 Place Doral FL 33172 USA ...

Reviews: