163
16.4.
13. J1 Malfunction
Malfunction conditions
When the outdoor pipe temperature is more than 65°C, the unit stops. It starts
again only when the outdoor pipe temperature is less than 52°C.
Possible causes
●
Faulty condenser temperature sensor
●
Dirty heat exchanger
●
System leakage or blockages
J1 displayed
J1 displayed
High temperature protection of
condenser
High temperature protection of
condenser
Is the condenser
temperature is Higher than
65°C?
Is the condenser
temperature is Higher than
65°C?
Yes
Is the resistance of
condenser temp. sensor
normal according
to
Appendix
1
Is the resistance of
condenser temp. sensor
normal according
to
Appendix
1
Replace the temperature sensor
Replace the temperature sensor
No
No
Is the outdoor ambient
temperature higher than
50
℃?
Is the outdoor ambient
temperature higher than
50
℃?
No
Stop the unit
Stop the unit
Yes
Is the outdoor unit ventilation
functioning properly?
Is the outdoor unit ventilation
functioning properly?
Yes
Ensure that the outdoor unit
ventilate is functioning properly
Ensure that the outdoor unit
ventilate is functioning properly
Is the heat exchanger dirty?
Is the heat exchanger dirty?
No
Clean the heat exchanger
Clean the heat exchanger
Yes
Check whether the refrigerant
system is functioning normally
Check whether the refrigerant
system is functioning normally
Replace outdoor main
board. Has the problem
been resolved?
Replace outdoor main
board. Has the problem
been resolved?
No
If the level of refrigerant is not
sufficient, does the system work after
refrigerant is added?
If the level of refrigerant is not
sufficient, does the system work after
refrigerant is added?
No
Is the outdoor fan running
properly?
Is the outdoor fan running
properly?
Refer to the solution to the
malfunction of fan speed being out of
control . Find the cause and resolve the
problem.
Refer to the solution to the
malfunction of fan speed being out of
control . Find the cause and resolve the
problem.
No
Yes
No
Correct the connection
Correct the connection
No
Yes
Is the connection between
temperature sensor and
PCB in working order?
Is the connection between
temperature sensor and
PCB in working order?
Yes
Summary of Contents for KDIP012-H2
Page 8: ...5 2 2 Part names of Indoor Outdoor units Cassette Units ...
Page 9: ...6 KDIR Duct Units ...
Page 10: ...7 KDIP Duct Units ...
Page 11: ...9 Ceiling floor Units ...
Page 12: ...10 HESP DUCT Units ...
Page 19: ...19 2 3 4 7 Outside Water Pump for Optional When Ceiling Installation ...
Page 31: ...33 KSIE024 H220 O KSIR036 H218 inch 37 2 16 1 31 9 40 6 26 5 15 9 ...
Page 34: ...36 Ceiling floor Units ...
Page 39: ...41 KTIR036 H2G1 KTIR048 H2G1 ...
Page 40: ...43 KUIR18 H2 KUIR24 H2 ...
Page 41: ...44 KFUF036 H2G1 KFUF048 H2G1 ...
Page 42: ...45 KFUF060 H2G1 ...
Page 43: ...46 KFUF036 H2G1 KFUF048 H2G1 ...
Page 44: ...47 KDIP090 H2 KDIP012 H2 KDIP018 H2 KDIP24 H2 ...
Page 69: ...74 6 2 Outdoor Unit KSIE018 H220 O KSIE024 H220 O ...
Page 70: ...75 KSIE009 H221 O KSIE012 H220 O ...
Page 71: ...77 KSIR036 H218 ...
Page 77: ...83 KDIR09 H2 Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 78: ...84 KDIR12 H2 Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 79: ...85 KDIR18 H2 Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 80: ...86 KDIR24 H2 Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 96: ...104 12 Field Wiring 9K 24K 36K 48K 60K ...
Page 97: ...105 ...
Page 147: ...155 P U P V ...
Page 148: ...156 P W P N ...
Page 181: ...191 4 Remove the evaporator fixing clamps to disassemble the evaporator Fixing clamps 1 screw ...
Page 188: ...221 5 Remove the four fixing screws of the fan motor then remove the motor 5 ...