108
5.Please refer to the following static pressure to
install.
Model
Static Pressure(Pa)
KDIR09-H2
KDIR12-
H2
0-45
KDIR18-H2
0-70
KDIR24-H2
0-100
KDIP018-H2
0-100
KDIP24-H2
0-160
KDIR036-H2G1
0-160
KDIR048-H2G1
0-160
Change the fan motor static pressure
corresponding to external duct static pressure.
NOTE: 1.Do not put the connecting duct weight
on the indoor unit.
2.When connecting duct, use inflammable
canvas tie-in to prevent vibrating.
3. Insulation foam must be wrapped outside the
duct to avoid condensate. An internal duct
underlayer can be added to reduce noise,
if the end-user requires.
13.2.1.5 Control (only for inverter KDIR Duct
units)
The capacity of the system and the
network address of the air-conditioner can
be set by the switches on the indoor Main
Control Board.
Before setting, turn off the power. After
setting, restart the unit.
Setting is not allowed when the unit is
power on.
1. Horsepower code setting
The capacity of the indoor unit has been set
in the factory according to the below table.
ENC1
Toggle switch
Code
Capacity(kw)
Note: The
capacity has
been set in the
factory, anyone
can’t adjust it
except the
qualified person
4
5.3
5.6
5
7.1
7
9.0
8
10.5
9
14
16
2. Network address set
Every air-conditioner in network has only one
network address to distinguish each other.
Address code of air-conditioner in LAN is set by
code switches S1 & S2 on the Main Control
Board of the indoor unit, and the set range is
0-63.
13.2.1.6
Adjust the air inlet direction (From
rear side to under-side)
For KDIR Duct units
①
Take off ventilation panel and flange, cut
off the staples at side rail
2. Stick the attached seal sponge as per the
indicating place in the following fig, and then
change the mounting positions of air return
panel and air return flange.
Summary of Contents for KDIP012-H2
Page 8: ...5 2 2 Part names of Indoor Outdoor units Cassette Units ...
Page 9: ...6 KDIR Duct Units ...
Page 10: ...7 KDIP Duct Units ...
Page 11: ...9 Ceiling floor Units ...
Page 12: ...10 HESP DUCT Units ...
Page 19: ...19 2 3 4 7 Outside Water Pump for Optional When Ceiling Installation ...
Page 31: ...33 KSIE024 H220 O KSIR036 H218 inch 37 2 16 1 31 9 40 6 26 5 15 9 ...
Page 34: ...36 Ceiling floor Units ...
Page 39: ...41 KTIR036 H2G1 KTIR048 H2G1 ...
Page 40: ...43 KUIR18 H2 KUIR24 H2 ...
Page 41: ...44 KFUF036 H2G1 KFUF048 H2G1 ...
Page 42: ...45 KFUF060 H2G1 ...
Page 43: ...46 KFUF036 H2G1 KFUF048 H2G1 ...
Page 44: ...47 KDIP090 H2 KDIP012 H2 KDIP018 H2 KDIP24 H2 ...
Page 69: ...74 6 2 Outdoor Unit KSIE018 H220 O KSIE024 H220 O ...
Page 70: ...75 KSIE009 H221 O KSIE012 H220 O ...
Page 71: ...77 KSIR036 H218 ...
Page 77: ...83 KDIR09 H2 Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 78: ...84 KDIR12 H2 Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 79: ...85 KDIR18 H2 Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 80: ...86 KDIR24 H2 Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 96: ...104 12 Field Wiring 9K 24K 36K 48K 60K ...
Page 97: ...105 ...
Page 147: ...155 P U P V ...
Page 148: ...156 P W P N ...
Page 181: ...191 4 Remove the evaporator fixing clamps to disassemble the evaporator Fixing clamps 1 screw ...
Page 188: ...221 5 Remove the four fixing screws of the fan motor then remove the motor 5 ...