PVH58 WALL THIMBLE INSTALLATION
An 11 inch square opening is required. Center Wall Thimble over the 11 inch square opening and secure both pieces on
either sides of the wall. Ensure that cutout is at the lower right corner, as electrical conduit must pass through this area.
PVH58 POWER
VENT
MOUNTING
Route wiring harness through wall thimble. Mount Power Vent unit onto building. Use silicone around Power Vent
mounting flange to provide waterproof seal. Secure venting to Power Vent by driving screws through
Vent Pipe Attachment
Straps.
All vent connections must be sealed with high temp sealant, such as Black Mill Pack.
Cutout At Lower
Right Corner when
looking into building.
Telescopic Wall Thimble
11” x 11” Framed
Opening In Wall
Apply Silicone
12” LENGTH OF HARD PIPE MUST
BE CONNECTED DIRECTLY TO
POWER VENT TO PASS THROUGH
WALL THIMBLE
Wiring Harness
Vent Pipe Attachment Strap – Secure to Venting
ALL VENT CONNECTIONS
MUST BE SEALED WITH HIGH
TEMP SEALANT, SUCH AS
BLACK MILL PACK.
Seal this area with silicone
once installation is complete
!
WARNING
Improper Installation may
cause water damage.
Use silicone sealant on Power
Vent mounting flange and
wiring harness opening.
Wiring Harness
Seal this area with silicone
once installation is complete
Vent Pipe
Attachment Strap
If you wish to use Flex Pipe,
connect adapters to end of 12”
hard pipe section (Refer to
Hard Pipe or Flex
section)
59
Summary of Contents for ZRB46
Page 31: ...Gas Conversion for Modulator PART C WARNING WARNING 31...
Page 41: ...Configuration 1 Basic manual HI LO and manual ON OFF capabilities 41...
Page 42: ...Receiver Module 584 523 521 221 1001 P221SI Receiver Module 584 523 521 221 1001 P221SI 42...
Page 63: ...PVCM Schematic Millivolt 63...
Page 67: ...PVCM Schematic IPI 67...
Page 68: ...68...