PVH58 VENTING CONFIGURATIONS
Refer to
Air Intake Adjustment
section of this manual to adjust Air
Intake Shutter.
PVH-58
Maximum / Minimum Vent Lengths:
Maximum
Vent Length is 125 ft plus six 90° elbows with Air Intake
Shutter fully closed. Termination must not be below unit.
This power vent can be installed up to 3ft below the installed fireplace
on runs less than 100ft and not more than four 90° elbows.
Minimum
Vent Length is 3ft horizontal plus minimum vertical rise with
Air Intake Shutter fully open.
MIN Venting= 3ft horizontal plus
minimum vertical rise with Air
Intake Shutter fully open
MAX Venting = 125ft
plus six 90° elbows
MAX 3ft Below Unit
Refer to fireplace manual for proper installation of your fireplace.
Minimum clearance to combustibles on venting is 1” unless otherwise stated in manual.
Refer to your fireplace manual for venting clearances up to 30 feet.
After 30ft of venting, clearance to combustibles is 1”.
PVH58 - Minimum Vertical Rise Before First 90° Elbow
(Measured from bottom of appliance to center of vent pipe)
ZRB46 None
Required
MQRB4436 37-1/2"
MQRB5143 51-1/2”
MQRB6961 56-1/2”
Seven 90° elbows are possible if
the total horizontal is not more than
25ft and the vertical does not
exceed 15ft.
NOTE:
MODELS EQUIPPPED WITH
MILLIVOLT/ STANDING PILOT
IGNITION:
Downward vertical vent runs are NOT
permitted.
NOTE:
MODELS EQUIPPPED WITH
INTERMITTENT PILOT IGNITION:
Downward vertical vent runs are
permitted, however, Cold Climate Switch
(Standing Pilot Mode) must not be used.
58
Summary of Contents for ZRB46
Page 31: ...Gas Conversion for Modulator PART C WARNING WARNING 31...
Page 41: ...Configuration 1 Basic manual HI LO and manual ON OFF capabilities 41...
Page 42: ...Receiver Module 584 523 521 221 1001 P221SI Receiver Module 584 523 521 221 1001 P221SI 42...
Page 63: ...PVCM Schematic Millivolt 63...
Page 67: ...PVCM Schematic IPI 67...
Page 68: ...68...