50
Installation of Side Wall Venting
The minimum distance from the bottom of fireplace to centre of vent is 51-1/2". For combustible walls: Cut a hole through
the wall allowing for an 11" x 11" (inside dimension) wall thimble. For a non-combustible wall: Cut an 8" diameter hole (see
Figure 4).
Note that the clearance to combustibles is stated the
Clearance to Combustibles
section of this Manual.
Select the approximate vent length, precise measurements are not needed as your flex pipe can be expanded to twice its
shipped length for ease of installation.
To install wall thimble centre over 11" x 11" framing from both sides of wall and secure. Route flex vent pipe through wall
thimble.
Note: Wall Thimble Shield [Z57WTS] must be used in Enclosures under 72”.
Before joining pipes, apply a bead of high temperature sealant (Mill Pac) to end of pipe. First attach the 5" flue pipe to the
vent termination with sealant, and secure with the four screws provided. At this time make sure the spacer springs are
attached to the 5" flex pipe as required. Then attach the 7" pipe by the same method.
Figure 4 - Side wall hole dimensions for
flush wall installations
.
For other installations where the unit is far away from the wall,
ensure that the vertical rise is 1/4" for every 12” of horizontal run.
Figure 5 - Venting configuration illustrating vertical rise over 4ft horizontal run.
Mount vent termination and seal to wall using caulking around the wall thimble to weather proof. After installing the vent
termination, double check to make sure the pipe extends properly through wall thimble and into vent termination.
Before joining pipes to fireplace flue, apply a bead of high temperature sealant (Mill Pac) to end of pipe. First attach the 5”
flue pipe to fireplace with sealant, and secure with the four screws provided. At this time verify that the spacer springs are
attached properly to the 5" flex pipe as required. Then attach the 7" pipe by the same method.
Support horizontal pipes every 2ft [61cm] with metal strap bands. Recheck fireplace to make sure it is leveled and properly
positioned and secured. Support vertical pipes to maintain a minimum of 1" or greater clearance to combustibles with metal
strapping bands.
Note: Vent Termination must not be recessed into wall or siding.
Summary of Contents for Marquis Infinite MQRB5143LP
Page 30: ...30 Millivolt System Lighting and Burner Control...
Page 39: ...39...
Page 41: ...41 Photos Bottom of Unit with IPI Module Light Module IPI Valve...
Page 42: ...42 Close up View of IPI Module Inside of IPI Module...
Page 43: ...43 IPI Valve IPI Valve...
Page 44: ...44 Millivolt Valve Light Module Millivolt Valve...
Page 49: ...49 Venting Examples All horizontal runs have a minimum rise per foot...
Page 57: ...57 Warranty...