Chapter 3: Configuration and commissioning
KFP-AF Series Installation Manual
49
Program options for output groups
Note:
This option is not available on repeater panels.
When configuring the operation mode of any output, there are three types of
output groups available: sounders, fire routing, and program (each program
group must be assigned a number - for example PRG1 - using the Group_n
option).
Outputs assigned to a program group (for example, PRG1) will be activated
depending on alarms in the fire network, in the local range of zones of the panel,
and with the corresponding delays.
For example, PRG1 may be configured to activate with a delay of 10 seconds for
an alarm in zones 120 to 139, with no delay for an alarm in zones 140 to 145,
and no activation for any other zones in the fire alarm panel (range 100 to 163 if
the initial zone is 100 and the panel is one loop).
This programmed output activation can be configured with the configuration utility
(recommended) or via the Delay configuration menu at the control panel.
Delay configuration
Note:
This option is not available on repeater panels.
Select this option to configure delays to activation of output groups. Delay
configuration options are shown in the table below.
Option Description
Sounders
Select this option to assign a global delay common to all the zones
configured to activate outputs with the operation mode Sounders
Fire routing
Select this option to assign a global delay common to all the zones
configured to activate outputs with the operation mode Fire routing
Program per zone
Select this option to assign, for a specific PRGn output group, different
activation delays per zone in alarm
Sounder and fire
routing per zone
Select this option to assign different activation delays per zone in alarm
for sounder or fire routing groups
Sounder and fire routing options
To configure a sounder or fire routing delay for all zones:
1. Select Field setup from the main menu
2. Select Delays configuration and then select Sounder or Fire routing
3. Enter the delay in seconds (for example, 120 seconds)
4. Select YES or NO for Activate for all zones
5. Press F4 (Enter) and then press F2 (Exit)
6. Press F1 (Keep), F3 (Apply), F4 (Discard), or F2 (Exit)
Once a delay has been configured, it must be enabled.
Summary of Contents for KFP-AF Series
Page 1: ...P N 501 405103 1 10 REV 1 0 ISS 20NOV09 KFP AF Series Installation Manual...
Page 16: ...Chapter 2 Installation 12 KFP AF Series Installation Manual Figure 4 Mounting hole locations...
Page 74: ...Appendix B Menu maps 70 KFP AF Series Installation Manual...
Page 77: ...KFP AF Series Installation Manual 73...
Page 78: ...74 KFP AF Series Installation Manual...
Page 79: ......
Page 80: ......