![Kilsen KFP-AF Series Installation Manual Download Page 18](http://html1.mh-extra.com/html/kilsen/kfp-af-series/kfp-af-series_installation-manual_1967144018.webp)
Chapter 2: Installation
14
KFP-AF Series Installation Manual
Connections
Recommended cables
Recommended cables for optimal system performance are shown in the table
below.
Table 3: Recommended cables
Cable
Cable requirements
Maximum cable length
Mains cable
3 x 1.5 mm
2
N/A
Loop cable
Twisted-pair (max. 52
Ω
/ 500 nF)
[1]
12 to 26 AWG (3.31 to 0.129 mm
2
)
2 km with KAL21 cable [1]
Fire network cable
Twisted-pair, CAT5
12 to 26 AWG (3.31 to 0.129 mm
2
)
1.2 km
Ethernet cable
Shielded CAT5
100 m
USB cable
Standard USB cable with A-B
connectors
10 m
[1] 26
Ω
per wire. Maximum cable length depends on the type of cable used and the loop load.
WARNING:
Other types of cable may be used subject to site-specific EMI
conditions and installation testing.
Securing cables
Use 20 mm cable glands to ensure clean and secure connections. All cables
should be fed through the cable guides in the cabinet housing to eliminate
movement.