Setup
Conditions
Symptoms
Diagnosis
Action to
Rectify
Notes
KiloVault®
HAB™ V4
units
connected in
parallel.
KiloVault®
HAB™ V4
units
charging.
1 or more
KiloVault®
HAB™ V4
units
stop charging.
Non-charging
KiloVault®
HAB™ V4 unit
's
"HT" light is lit.
Non-charging
KiloVault®
HAB™ V4 unit
's
ALARM LED is
flashing.
Rest of
KiloVault®
HAB™ V4
units
continue
charging and
their RUN LEDs
are lit.
When high
temperature
protection is
released, the
ALARM LED
will go out
and the RUN
LED will start
flashing 1s on,
1s off as it
waits to be
added back
into parallel
connection.
6.4.
Resetting / Recalibrating the KiloVault® HAB™ V4
The following section describes the reset / recalibration process.
6.4.1.
Resetting the KiloVault® HAB™ V4
If necessary, you can reset the KiloVault® HAB™ V4 by first turning it on using
the front power button, and then pressing and holding down the power button
for 10 seconds. This will clear any alarms and protection locks. This
will not
reset the cycle count.
6.4.2.
Recalibrating the KiloVault® HAB™ V4