47 of 56
Revision 4
KiloVault
®
LLC • 330 Codman Hill Road, Boxborough, MA 01719 • +1 (888) 218-5924 •
• www.kilovault.com
Setup
Conditions
Symptoms
Diagnosis
Action to
Rectify
Notes
KiloVault®
HAB™ V4
unit
s
connected in
parallel.
KiloVault®
HAB™ V4
unit
s have
similar
voltages.
Leader
KiloVault®
HAB™ V4
outputs power.
Follower
KiloVault®
HAB™ V4 unit
s
do not output
power
All KiloVault®
HAB™ V4
LCD
Screens are lit.
Leader RUN LED
is ON.
Follower RUN
LEDs are OFF.
One or more
follower ALARM
LEDs flash 0.5s
on, 0.5s off.
Follower
Communicati
on ID Address
Repeated.
More than
one follower
KiloVault®
HAB™ V4
has
the same
address.
Check the
addresses of
the
KiloVault®
HAB™ V4
unit
s with
the alarms.
Set each to a
unique
address.
Restart the
KiloVault®
HAB™ V4
unit
s using
the front
panel power
switch.
If the problem
persists, you
have the option
of operating your
bank without
interbattery
communication.
You can do this
by removing all
of the KiloVault®
HAB™ V4 to
KiloVault® HAB™
V4
communication
cables, removing
all of the
communication
port terminators,
and setting each
KiloVault® HAB™
V4 units address
to (OFF, OFF, OFF,
OFF), (0,0,0,0).