Alarm / Protection Condition
Trigger Values
High Voltage release method
Under the release voltage (54.4
V±0.5 V) for 1s
Low Displayed Capacity Alarm
10% of Capacity or lower
Low Voltage alarm for each cell
3.00±0.03 V
Low Voltage protection for each cell
2.70±0.03 V, Delay time: 1s
Low Voltage release for each cell
3.10±0.03 V
Low Voltage alarm for total voltage
48.0 V±0.5 V
Low Voltage protection for total voltage
43.2 V±0.5 V, Delay time: 1s
Low Voltage release for total voltage
49.6 V±0.5 V
Low Voltage release method
Charge to recovery
Charge over current alarm
165±5 A
Charge over current protection
180±5 A, Delay time: 5s
Charge over current release method
Auto release after 1min
Discharge over current alarm
165±5 A
Discharge over current protection
180±10 A, Delay time: 1s
Over current release method
Auto release after 1min
Charge High Temperature alarm
122°F ± 5.4°F (50°C ± 3°C)
Charge High Temperature protection
131°F ±5.4°F (55°C ± 3°C)
Charge High Temperature release
113°F ±5.4°F (45°C ± 3°C)
Discharge High Temperature alarm
140°F ±5.4°F (60°C ± 3°C)
Discharge High Temperature protection
149°F ±5.4°F (65°C ± 3°C)
Discharge High Temperature release
131°F ±5.4°F (55°C ± 3°C)
Charge Low Temperature Alarm
37.4°F ±5.4°F (3°C ± 3°C)
Charge Low Temperature Protection
32°F ±5.4°F (0°C ± 3°C)
Charge Low Temperature Release
41°F ±5.4°F (5°C ± 3°C)
Discharge Low temperature alarm
5°F ± 5.4°F (-15°C ± 3°C)
Discharge Low temperature protection
-4°F ± 5.4°F (-20°C ± 3°C)