48 of 56
Revision 4
KiloVault
®
LLC • 330 Codman Hill Road, Boxborough, MA 01719 • +1 (888) 218-5924 •
• www.kilovault.com
Setup
Conditions
Symptoms
Diagnosis
Action to
Rectify
Notes
KiloVault®
HAB™ V4
unit
s
connected in
parallel.
KiloVault®
HAB™ V4
unit
s with
similar
voltages
Leader
KiloVault®
HAB™ V4
outputs power.
Follower
KiloVault®
HAB™ V4 unit
s
do not output
power
All KiloVault®
HAB™ V4
LCD
Screens are lit.
Leader RUN LED
is ON. Follower
RUN LEDs are
OFF. One or
more follower
ALARM LEDs
flash 0.5s on,
0.5s off.
The followers
with the
flashing
ALARM LEDs
have lost
communicatio
n with the
Leader
KiloVault®
HAB™ V4
.
Ensure the
KiloVault®
HAB™ V4
to
KiloVault®
HAB™ V4
communicati
on cables
between
KiloVault®
HAB™ V4
unit
s are
secure and
the RJ45 120
Ω Resistor
Plug
retention
clips are
locked.
If the
retention
If necessary,
disconnect all
communication
cables from each
other, set each
unit address to
(0,0,0,0) and
operate the bank
like a non-smart
bank of parallel
batteries.