38 of 56
Revision 4
KiloVault
®
LLC • 330 Codman Hill Road, Boxborough, MA 01719 • +1 (888) 218-5924 •
• www.kilovault.com
Device
Setting
Under 40A
Charger
40-60A
Charger
60-150A
Charger
Peukert
Coefficient
1.05
Internal
Resistance
≤15mΩ
Recommended
Charge Current
100 Ah per KiloVault® HAB™ V4 in Parallel
(Solar Charge Controller Amps + Percentage of
Inverter/Charger Maximum DC Output).
Example: For a single KiloVault® HAB™ V4
system with an inverter/charger maximum DC
output of
100 A and a solar charge controller capable of
50 A, limit the inverter/charger output to 50 A
(so the total is 100 A).
Inverter
Charger
Absorb Time
(some controllers
do not allow a
selection under 6
minutes, please
contact KiloVault
for additional
information)
Under 6
minutes
Under 4
minutes
Under 2
minutes
Battery Capacity
150 Ah (7.5 kW) per KiloVault® HAB™ V4
Battery Type
Lithium Ion or Custom - whichever provides
access to the required settings
Absorption
56 V
Bulk (98% to
100% of
Absorption)
56 V
Bulk Current
75 A
Charge Cycle
2 Stage No Float
HBCO (High
Battery Cut Out)
57 V (58V for Schneider Equipment)
LBCO (Low
Battery Cut Out)
48.2 V (48V for Schneider Equipment)
LBCO Delay
3 seconds