PMX_MULTI
User’s Manual
19
Installation
Connecting to the Output Terminals
When using the sensing function, connect the sensing cables before connecting the load cables to the out-
put terminals.
1
Turn the POWER switch off.
2
Attach crimping terminals to the load cables.
3
Remove the knobs once, and attach the load cables to the output terminals.
Connect the short bar to the negative or positive output terminal.
If you are not grounding the output terminal (leaving it floating), follow the instructions in see “When
the output terminal is not grounded (floating)” on page 17 before use.
To reduce the influence of noise on the output, keep the cables as short as possible. If possible,
twist the positive and negative load cables.
4
To attach the output terminal cover, remove the chassis terminal screws on the out-
sides.
WARNING
Risk of electric shock.
• Turn the POWER switch off before you touch the output terminals.
• Regardless of whether load cables are connected to the output terminals, be sure to
attach the output terminal cover before turning the POWER switch on.
M6
Crimping terminal
Output terminal knob
Example of PMX32-2QU
To attach the output terminal cover,
remove these screws.
Example of PMX32-2QU