Page 14 / 26
Product Description
SBM51/06
Datasheet 2.50-40.051-71-EN
First DDC Software Menu M090 and CD_SB51 (Odd-Numbered Addresses)
Menus /01, /03, /05, /07, /09, /11, /13, /15 --- Danfoss frequency inverter VLT 5000, VLT 6000,
VLT 2800, FC 102, FC 202, FC 301, FC 302, FC 51
NOTE
The Danfoss frequency inverters that can be connected to the SBM51/06 do not support all possible
parameters (see parameter reference tables from page 22).
Parameter 2209 “External System OK”
Is set to “0” when the communication to the external system is interrupted.
Parameter 2251 “Analog Actual Value 4”
Counts the operating hours of the connected motor.
Parameter
Plain text
Meaning
Unit
2209
External system ok (only DDC3000) Participant is registered
-
2210
Analog actual value 1
FI type
-
2211
Analog actual value 2
Voltage type
-
2212
Analog actual value 3
Service life
h
2251
Analog actual value 4
Operating time
h
2215
Analog actual value 5
Rated motor speed
rpm
2252
Analog actual value 6
Absolute speed
rpm
2253
Analog actual value 7
User-defined display
-
2254
Analog actual value 8
Relative rotary frequency
%
2255
Analog actual value 9
Absolute rotary frequency
Hz
2256
Analog actual value 10
Motor current IRMS
A
2257
Analog actual value 11
Performance
kW
2258
Analog actual value 12
Energy consumption
kWh
2240
Q analog setpoint 1
Relative setpoint rotary frequency
%
2241
Q analog setpoint 2
Minimum setpoint PS1
Hz
2242
Q analog setpoint 3
Maximum setpoint PS1
Hz
2222
Digital actual value 1
Error/malfunction
-
2224
Digital actual value 2
General warning
-
2225
Digital actual value 3
Ready for operation
-
2226
Digital actual value 4
switched on
-
2227
Digital actual value 5
Setpoint reached
-
2228
Digital actual value 6
Warning
Load shedding
-
2216
Q digital setpoint 1
Motor enable
-
2220
Q digital setpoint 2
Freewheel stop
-
2245
Q digital setpoint 3
Malfunction acknowledgment
-
2246
Q digital setpoint 4
Parameter set selection
-
2217
Operating mode
Stop, automatic, manual
1 = Stop
7 = Auto
8 = Manual
-