Product Description
SBM51/06
Datasheet 2.50-40.051-71-EN
SBM51/06 Parameter Description
Content of the parameter description
The
parameter description
contains information regarding SBM51/06 DDC3000/DDC4000 system
parameterization.
Firmware version
This parameter description describes SBM51/06 firmware as of version 6.0.
NOTE
When using frequency inverters, it may, depending on the series and the application, be necessary
to take interference suppression measures. In this case, please contact Danfoss.
!
NOTICE
Per DDC3000/DDC4000 system, a maximum of five SBM51, regardless of type, may be connected
to the switch cabinet bus.
Basic Program
Registering the SBM51/06 on the DDC
After switching the supply voltage on, the SBM51/06 checks the availability of the switch cabinet bus
and uses the basic program to register with the DDC3000/DDC4000 automation system. In addition,
the SBM51/06 automatically registers the connected frequency inverter with the DDC.
Parameter List in the DDC3000 System
The SBM51/06 basic program contains the following parameters:
These parameters apply for all Danfoss frequency inverters connected to the SBM51/06.
Parameter 899 “Central unit/KK version”
In parameter 899 Central unit/KK version, the SBM51/06 registers its firmware version.
Parameter 2202 “Q Bus Mode”
Parameter 2202 Q bus mode turns the communication for the bus system (FC bus) on or off:
■
“0”
→
FC bus OFF
■
“1”
→
FC bus ON.
Parameter 2203 “Q Cycle”
The parameter 2203 Q cycle is
not
needed for SBM51/06.
Parameter 2204 “Foreign Bus OK”
In parameter 2204 foreign bus OK, the SBM51/06 registers malfunctions on the FC bus:
■
“1”
→
The FC bus is working without errors.
■
“0”
→
Errors occurred on the FC bus.
Parameter
No.
Parameter plain text
Value range
(Initial value)
899
Central unit/KK version
Text (invalid)
2202
Q bus mode
0; 1 (0)
2203
Q cycle
0; 1 (0)
2204
Foreign bus OK
0; 1 (invalid)