Datasheet 2.50-40.051-71-EN
SBM51/06
Product Description
Parameter 2215 “Analog Actual Value 5”
Parameter 2215 is only read once when the FI is registered. If the parameter is changed during
operation, the new value is only valid when the FI has been registered again.
Parameter 2253 “Analog Actual Value 7”, 2254 “Analog Actual Value 8” and 2240 “Q Analog
Setpoint 1”
Further parameterization information can be found in the following project planning sections.
Parameter 2222 “Digital Actual Value 1”
The FI switches off in the event of a malfunction. The malfunction must be acknowledged via digital
setpoint 3 (2245) = 1. Remedy the cause of the error before acknowledgment.
Parameter 2224 “Digital Actual Value 2”
Warning messages are automatically canceled when the operating conditions are back within the
normal range.
Parameter 2217 Operating mode
Auto = Motor running
Stop = Motor not running
Manual = FI is in manual mode
Parameter 2241 “Q Analog Setpoint 2” and 2242 “Q Analog Setpoint 3”
Contain the setpoint limits for parameter set 1.