A
Page 24 / 26
Product Description
SBM51/06
Datasheet 2.50-40.051-71-EN
Parameter Reference Table
Software Menu M090 and CD_SB51: /01, /03, /05, /07, /09, /11, /13, /15 --- Danfoss frequency
inverters FC-102/FC-202, FC-301/302, VLT Micro Drive FC 51
Para
meter
DDC Parameter Text Meaning
FC-102/
FC-202
Data Points
FC-301/
FC-302
Data Points
VLT Micro
Drive FC 51
Data Points
2210
Analog actual value 1 FI type
15-40
15-40
15-40
2211
Analog actual value 2 Voltage type
15-42
15-42
15-42
2212
Analog actual value 3 Service life
15-00
15-00
15-00
2251
Analog actual value 4 Operating time
15-01
15-01
15-01
2215
Analog actual value 5 Rated motor speed
1-25
1-25
1-25
2252
Analog actual value 6 Speed calculated
16-17
16-17
-
2253
Analog actual value 7 User-defined display
16-09
16-09
16-09
2254
Analog actual value 8 Relative rotary
frequency
State word/
output
frequency
State word/
output
frequency
State word/
output
frequency
2255
Analog actual value 9 Absolute rotary
frequency
16-13
16-13
16-13
2256
Analog actual value 10 Motor current IRMS
16-14
16-14
16-14
2257
Analog actual value 11 Performance
16-10
16-10
16-10
2258
Analog actual value 12 Energy consumption
15-02
15-02
15-02
2240
Q analog setpoint 1
Relative setpoint
rotary frequency
Control word/
setpoint
frequency
Control word/
setpoint
frequency
Control word/
setpoint
frequency
2241
Q analog setpoint 2
Minimum setpoint
PS1
3-02
3-02
3-02
2242
Q analog setpoint 3
Maximum setpoint
PS1
3-03
3-03
3-03
2222
Digital actual value 1
Error/malfunction
State word.
03/04
State word. 03/
04
State word.
03/04
2224
Digital actual value 2
General warning
State word.
07
State word. 07
State word.
07
2225
Digital actual value 3
Ready for operation
State word.
01
State word. 01
State word.
01
2226
Digital actual value 4
switched on
State word.
11
State word. 11
State word.
11
2227
Digital actual value 5
Setpoint reached
State word.
08
State word. 08
State word.
08
2228
Digital actual value 6
Warning
Load shedding
Warning
word 2. 08
-
-
2216
Q digital setpoint 1
Motor enable
Control word.
06
Control word.
06
Control word.
06
2220
Q digital setpoint 2
Freewheel stop
Control word.
03
Control word.
03
Control word.
03
2245
Q digital setpoint 3
Malfunction acknowl-
edgment
Control word.
07
Control word.
07 (Reset)
Control word.
07 (Reset)
2217
Operating mode
Stop, manual, auto-
matic
State word.
11/09
State word. 11/
09
State word.
11/09