Product Description
SBM51/06
Datasheet 2.50-40.051-71-EN
Second DDC Software Menu M090 and CD_SB51 (Even-Numbered Addresses)
Menus /02, /04, /06, /08, /10, /12, /14, /16 --- Danfoss frequency inverter VLT 5000, VLT 6000,
VLT 2800, FC 102, FC 202, FC 301, FC 302, FC 51
NOTE
The Danfoss frequency inverters that can be connected to the SBM51/06 do not support all possible
parameters (see parameter reference tables from page 22).
Parameter 2241 “Q Analog Setpoint 2” and 2242 “Q Analog Setpoint 3”
Contain the setpoint limits for parameter set 2.
Parameter 2240 “Q Analog Setpoint 1”
Special features for registering/deregistering FIs in the event of invalid parameter 2240 configuration
in the second DDC software menu:
■
If “1” - “4” (no external selection) is configured as a parameter set in the FI, the SBM is in actual
value mode and parameter 2240/02 is not relevant.
When the FI is registered again:
■
If an external selection is configured as a parameter set in the FI and the parameter 2240/02 has
the values “0”, > “4” or “invalid”, the SBM switches to actual value mode and returns the value “0”
for parameter 2211/02.
Parameter
Plain text
Meaning
Unit
2209
External system ok (only DDC3000) Participant is registered
-
2211
Analog actual value 2
Active parameter set
-
2251
Analog actual value 4
Setpoint error
-
2215
Analog actual value 5
Actual value error
-
2252
Analog actual value 6
Rel. error
-
2253
Analog actual value 7
Analog input terminal 54
V
2254
Analog actual value 8
Motor voltage
V
2255
Analog actual value 9
Minimum setpoint
Hz
2256
Analog actual value 10
Maximum setpoint
Hz
2240
Q analog setpoint 1
Parameter set selection, actual
value mode
-
2241
Q analog setpoint 2
Minimum setpoint PS2
-
2242
Q analog setpoint 3
Maximum setpoint PS2
-
2222
Digital actual value 1
Mains phase error
-
2224
Digital actual value 2
Thermal warning
-
2225
Digital actual value 3
Voltage high/low
-
2226
Digital actual value 4
Not in freq. range
-
2227
Digital actual value 5
Dig. input terminal 32
-
2228
Digital actual value 6
Dig. input terminal 33
-
2216
Q digital setpoint 1
Relay 1 on
-
2220
Q digital setpoint 2
Relay 2 on
-
2245
Q digital setpoint 3
Activate relay
-
2246
Q digital setpoint 4
DC brake
-
2217
Operating mode
Stop, automatic, manual
1 = Stop
7 = Auto
8 = Manual