TM0066
Page 30 of 39
Issue 2.01
INTERNAL INDICATIONS
LED 1
PS
Power supply fault
LED 2
ALM
Alarm fault
LED 3
DSP
Display disconnected
LED 4
-
Earth fault
EXTERNAL DIMENSIONS - 370(h) X 330(w) x 113 (d) mm
WEIGHT - 6 kg (excluding batteries)
BATTERY CAPACITY
2 X 12V 6 Ah Yuasa sealed lead acid cells
Replacement period
4 years
CURRENT CONSUMPTION
Quiescent current
86 mA
Alarm current
195 mA (no sounder load)
Maximum power supply output is rated at 1.5 Amps
EXTERNAL DIMENSIONS - 276(h) X 306(w) x 100 (d) mm
WEIGHT - 4 kg (excluding batteries)
BATTERY CAPACITY
2 X 12V 3.2 Ah Yuasa sealed lead acid cells
Replacement period
4 years
CURRENT CONSUMPTION
Quiescent current
111 mA
Alarm current
237 mA (no sounder load)
Maximum power supply output is rated at 3.1 Amps