TM0066
Page 23 of 39
Issue 2.01
activated but the sounder circuits and the auxiliary contacts will remain unoperated.
-
To re instate a zone from the test mode to its normal condition select the required
zone number and operate the enter key. Revert SW1 leaf 3 to the off position to
disable the test mode.
3.5
RELAY ISOLATE
-
The operation of the relay isolate button will disable all auxiliary contacts and operate
the disablement LED in a constant mode with the internal buzzer operating in an
intermittent mode.
-
The relay isolate button will operate as a toggle to isolate and reinstate the auxiliary
relays as required.
3.6
DEFINITIONS
-
Pulsed
=
1 second on, 1 second off.
-
Intermittent
=
1 pulse every 15 seconds.
-
Slow pulse
=
1 pulse every 5 seconds.
-
The membrane incorporates two user LED's which can be activated by the application
of 0V into the appropriate input terminal on the main PCB. These LED's are to be
illuminated during the panel lamp test (reset).
Summary of Contents for SIRIUS