TM0066
Page 31 of 39
Issue 2.01
5.3
8 ZONE PANEL
TERMINALS
Note
All terminals are capable of accepting conductors of cross
sectional area 1.0 - 2.5 mm.
Mains Block
Live, neutral and earth 240V a.c. + 10%/-15%, 50/60Hz.
Common Fault Relay
Single pole changeover rated at 30V 1 Amp.
Common Fire Relay 1
Single pole changeover rated at 30V 1 Amp.
Common Fire Relay 2
Single pole changeover rated at 30V 1 Amp.
Auxillary Supply
0V and 24V d.c. output terminals rated at 500 mA.
Sounder Circuit 1
Reverse polarity monitored circuit rated at 750 mA.
Sounder Circuit 2
Reverse polarity monitored circuit rated at 750 mA.
Repeat outputs
Common fault and zones 1 - 8 repeat rated at 100 mA.
Remote Inputs
Evacuate, silence and reset terminals which require a 0V to
activate them.
User LEDs 1 & 2
0V input required to activate the LEDs located on the
membrane.
Zones 1 - 8
+ & - per zone, each rated at 5 mA with a maximum of 20
detectors per zone.
Battery
+ & - input terminals which can receive a maximum of 1000
mA from the charger.
Fault Input
0V input requires to drive common fault indication.
Evac. Output
0V output to sound alarms mode.
Silence Output
0V output to silence alarms mode.
Reset Output
0V output in Reset mode.
NOTE:
The remote inputs and outputs are for internal use only.
INTERNAL CONTROLS
SW1
4 Way DIL switch
Leaf 1 OFF
Sounder circuits constant
Leaf 1 ON
Sounder circuits pulsed
Leaf 2 ON
Zone 1 non latching mode
Leaf 3 ON
Initiates the test mode
Leaf 4 ON
Operates the processor fault counter
Summary of Contents for SIRIUS
Page 1: ...TM0066 Page 1 of 39 Issue 2 01 SIRIUS MANUAL TM0066 Main Menu Exit ...
Page 8: ...TM0066 Page 8 of 39 Issue 2 01 THIS PAGE IS INTENTIONALLY BLANK ...
Page 20: ...TM0066 Page 20 of 39 Issue 2 01 THIS PAGE IS INTENTIONALLY BLANK ...
Page 24: ...TM0066 Page 24 of 39 Issue 2 01 THIS PAGE IS INTENTIONALLY BLANK ...