KEY RK-2006LSPz Operation Manual Download Page 27

27

6. Room thermostat.

RK-2006LSP controller is fitted with the input that enables connection of any room

thermostat provided with contact output. If room temperature is lower from the

required one (closed contacts) light on the room thermostat will be switched on. This

means that the boiler will maintain the setting programmed with knob. When the

required room temperature is obtained the light will be switched off and the boiler will

be switched into EXTINCTION (SHUT DOWN) mode.

CAUTION!

If room thermostat is not used this input shall remain closed (by installing

jumper). In this case the boiler operation will maintain temperature setting

programmed with the knob.

CAUTION!

Room thermostat input is active during work in WINTER mode only.

7. DATA emergency output - audible alarm or cleaning mechanism.

The regulator has output DATA allows you to connect via the UM-1 module siren

alarm or additional cleaning mechanism. If you exit this mode, the siren is in alarm, it

is activated in the event of: sensor failure of the boiler, burner sensor, the sensor or

mixing pump hot water, boiler overheating or lack of fuel.

8. Controller disassembly.

If controller disassembly is necessary follow the following procedure:

- Disconnect the boiler and controller from power supply,

- Remove the controller from the boiler,

- Disconnect terminals and wires from the controller.

9. Technical Data.

Power Supply

230V ± 10%, 50Hz

Power consumption (without fan and pump)

< 4VA

Burner temperature measurement range (KTY 81-210)

-9–109°C

±1°C

Temperature measurement range (KTY 81-210)

-9–109°C

±1°C

Burner temperature measurement range (PT-1000)

-30–500°C ±3°C

Boiler temperature adjustment range

30–90°C

±1°C

Boiler programmed overheating protection

90–99°C

±1°C

Boiler equipment overheating protection

>95°C

±1°C

Total outputs rating

max 4A/230V

Dimensions (H x W x D)

96x144x94

Summary of Contents for RK-2006LSPz

Page 1: ...OPERATION MANUAL RK 2006LSPz AUGER FITTED SOLID FUEL BOILER TEMPERATURE CONTROLLER Version C820...

Page 2: ......

Page 3: ...electrical connection diagram For connection of stoker alarm indicator and ash removal system the additional module UM 1 shall be applied CAUTION Before plugging in the controller first check if the...

Page 4: ...ere is 1 Display 2 Fan indicator 3 Auger indicator 4 Ignition glow plug indicator 5 Central heating circuit pump indicator 6 Hot tap water pump or mixing pump indicator 7 Room thermostat operation and...

Page 5: ...ration mode Description STOP Boiler control stopped Controller maintains central heating and domestic water pump operation but automatic ignition does not follow STAND BY Controller maintains central...

Page 6: ...the technician IGNITION mode follows till flame is detected If the flame is not detected within the specified time the controller activates Out of fuel alarm Pressing STOP button exceeding time limit...

Page 7: ...ustion and the burner cool down Fan power when in EXTINCTION SHUT DOWN mode is determined by the technician When EXTINCTION SHUT DOWN is finished the controller is switched into CLEANING STAND BY or S...

Page 8: ...s by pressing START button A L A RM O U T O F F U E L Emergency alarm Depending on construction type the boiler may be equipped with emergency sensor e g hopper cover sensor Activation of the alarm wi...

Page 9: ...creases above 93 C it will activate STB system which will automatically engage power for central heating pump and will shut off blower Operation of STB will result in switching the controller to STAND...

Page 10: ...omatically if repairs are made 4 Review of user settings Pressing parameter buttons 8 and 11 allows reviewing user s parameters while their activation is indicated with fast flashing of proper light F...

Page 11: ...work time Burner start up counter 4 1 Fuel type selection RK 2006LSP controller enables programming ignition settings for four different fuel types Fuel type parameter enables switching between partic...

Page 12: ...n follow at the same time H O T W A T E R P R I O R I T Y N O Bacterial flora liquidation in domestic water tank the controller enables manual activation of program for bacterial flora liquidation in...

Page 13: ...ion of the temperature detector of burner fuel ignition If the system is fitted with optical fire burner detector parameters change and viewing is unavailable Burner measured temperature this paramete...

Page 14: ...setting Table 3 Service settings Light Parameter Min Max No Language selection See description Fan Fan modulation during boiler start NO YES Min fan speed during heating up 1 100 Max fan speed during...

Page 15: ...xtension time 1min 10min Mixing pump engaging temperature 30 C 60 C Mixing pump work hysteresis 1 C 9 C Thermostat Boiler minimum temperature 30 C 69 C Boiler maximum temperature 70 C 90 C Boiler uppe...

Page 16: ...increase fan speed up to the selected Max fan speed during boiler start setting I G N I T I O N M O D U L S T A R T D E L A Y 5 0 s Fan speed during ignition this parameter describes power of the fan...

Page 17: ...venge This setting is unavailable if Fan scavenge air purging setting was not selected F A N S C A V E N G E P A U S E T I M E 1 m i n Fan speed during scavenge air purging this parameter specifies fa...

Page 18: ...programmed setting specifies feeding time in percent in relation to the time of whole work cycle F U E L D O S E F O R M A X P O W E R 5 0 Fuel feed for min burner power this parameter specifies fuel...

Page 19: ...hed off S T O K E R E M P T Y I N G T I M E 4 0 s Auger ignition test this parameter provides functionalities of X emergency input If NO setting was selected then X input will be used for connection o...

Page 20: ...lame of the light equals zero F D 1 C O R R E C T I O N 0 Hysteresis loss of flame depending on the type of flame detector this parameter specifies how many degrees or units in relation to the thresho...

Page 21: ...ng mechanism In this case the output DATA is working as an external alarm CYCL means the mode in which the cleaning procedure is run after the firing and repeated at regular intervals until burner shu...

Page 22: ...ies the minimum number of hours the burner must in order to start cleaning If the minimum time is not reached the cleaning will not run even if there was a required number of shut downs Setting the pa...

Page 23: ...y heating system is provided with domestic water tank and charge pump this circuit may be switched off or used for control of the pump that mixes the return water in the boiler Domestic water path if...

Page 24: ...ng is available if domestic water path EXISTS setting was selected H W P U M P W O R K E X T E N S I O N Y E S Domestic water pump extension time this parameter specifies the time lapse when domestic...

Page 25: ...burner extinction shut down B O I L E R U P P E R H Y S T E R E S I S 5 c Burner power switching hysteresis when the programmed boiler water temperature is obtained the controller is switched to mini...

Page 26: ...will result in cancelling of all parameters and restoration of default parameters programmed before by the fitter or technician S E R V I C E S E T T I N G S N O CAUTION Activation of this function wi...

Page 27: ...has output DATA allows you to connect via the UM 1 module siren alarm or additional cleaning mechanism If you exit this mode the siren is in alarm it is activated in the event of sensor failure of th...

Page 28: ...28 Figure 2 RK 2006LSP Controller connection diagram...

Page 29: ...Settings 1 2 3 4 Thermostat Boiler max power HTW pump Domestic water desired temperature Domestic water heating priority Igniter Brightness when fuel ignition has occurred FD 1 Burner temperature with...

Page 30: ...Fan scavenge air purging Fan scavenge air purging blow time Fan scavenge air purging pause time Fan speed during scavenge Auger Auger filling time Initial fuel feed Fuel feed cycle Fuel feed during i...

Page 31: ...out cleaning CH pump Central heating pump work mode Central heating pump periodic work Central heating pump periodic work time HTW pump Domestic water path Domestic water heating hysteresis Boiler inc...

Page 32: ...32...

Page 33: ...33...

Page 34: ...34...

Page 35: ...0 4 11 2005 U PN EN 60730 1 2002 A1 2006 U A12 2004 A13 2005 PN EN 60730 1 2005 A14 2006 PN EN 60730 2 9 2006 PN EN 61000 3 2 2006 U PN EN 61000 3 3 1997 A1 2005 A2 2006 IS1 2006 Information on dispos...

Page 36: ...Manufacturer Przedsi biorstwo Wielobran owe KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Reviews: