Table 2. User settings list.
Light
Parameter
Min.
Max.
Auger
Fuel type.
1
4
Thermostat Desired boiler temperature.
40°C
90°C
Boiler max. power.
60%
100%
CH pump
Central heating pump operation mode.
WINTER
SUMMER
HTW
pump
Domestic water desired temperature.
30°C
60°C
Domestic water heating priority.
NO
YES
Domestic water tank bacterial flora liquidation program.
NO
YES
Measured domestic water temperature.
Measured return water temperature.
Igniter
Current furnace brightness (FD-1).
Brightness when fuel ignition has occurred (FD-1).
0
255
Temperature of the burner (PT-1000, CT-1/2).
Burner temperature with fuel ignited (PT-1000, CT-1/2).
20°C
20°C
500°C
100°C
Burner work time.
Burner start up counter.
4.1. Fuel type selection.
RK-2006LSP controller enables programming ignition settings for four different
fuel types. „Fuel type” parameter enables switching between particular settings. Fan,
auger and igniter operation are saved for the selected fuel type.
F U E L
T Y P E
1
CAUTION!
Fuel type may be changed, if the controller is in STOP mode only.
4.2. Boiler temperature setting.
Desired boiler temperature
- it is the temperature setting that will be obtained by
the controller, if room thermostat input contacts are closed.
D E S I R E D B O I L E R
T E M P E R A T U R E
5 0 c
4.3. Boiler operation max. power.
Boiler operation max. power
- this parameter enables to limit boiler operation max
power. Power limitation is possible thanks to fuel reduction during operation at
maximum power.
M A X I M U M B O I L E R
P O W E R
1 0 0 %