background image

6

are abrasive, corrosive, liquids or detergent.

•  when it is needed to remove the protection cover to access to 

the terminals, they will have to be put back before starting up the 
equipment. otherwise you may incur personal injury or equip-
ment damage.

•  be careful to not lift heavy loads without help, according to the 

following recommendations:

 

ˆ

, < 18 kg.

 

ˆ



, 18 - 32 kg.

 

ˆ



, 32 - 55 kg.

 

ˆ

, > 55 kg.

•  UPSs are electronic equipments, so they will be treated as they 

are:

 

ˆ

Avoid shocks.

 

ˆ

Avoid jolting or bouncing of the UPS, like those produced by 
moving the equipment on a hand truck and move on an un-
even or wavy surface.

•  UPS transport will be done packaged inside its original packaging 

in order to prevent it from shock and impact and by means of the 
suitable type of packaging (carton box, pallet packaging, ...) and 
appropriate to its weight.

•  Although the physical location of the elements can differ from 

the illustrations in this manual in some cases, the correct labelling 
correct the possible doubts and makes easy its comprehension.

1.2.3.3.  Safety warning regarding batteries

• 

The manipulation and connection of the batteries shall 
be done and supervised by personnel with battery 

knowledge only.
before doing any action, disconnect the batteries. Check that no 
current is present and there is not dangerous voltage in the DC 
bUS (capacitors) or in the endpoint of the battery set terminals.
battery circuit is not isolated from input voltage. Dangerous volt-
ages can be found between the terminals of the battery set and 
the earth. Check that there is not any voltage at the input before 
take any action over them.

•  when faulty batteries are replaced, the complete battery set has 

to be replaced, less exceptional cases in new equipments, were 
due to manufacturing faults it will only be replaced the defective 
ones.
The replacement will be done by another one of the same type, 
voltage, capacity, quantity and brand. All of them has to be of the 
same brand.

•  Generally, the used batteries are sealed lead acid of 12V and 

maintenance free (VRlA).

•  Do not reuse the faulty batteries. There could be an explosion 

or burst any battery with the involved problems and issues that 
could happen.

•  Generally supplied batteries are installed in the same cabinet, 

case or rack of the equipment. Depending on the power, au-
tonomy or both, they can be supplied separately from the equip-
ment in another cabinet, case or rack, with the interlink cables 
among them. Do not modify its length.

•  in those equipments requested without batteries, their acquisi-

tion, installation and connection of themselves will be done by 
the end-user and under his responsibility. Data concerning the 
batteries as regards to quantity, capacity and voltage, are stated 

in this battery label sticked beside the nameplate of the equip-
ment. Respect these data, battery connection polarity strictly.
For an optimum and efficient operating, the battery set has to be 
located as close as possible to the equipment.

• 

The battery voltage can involve the risk of electric shock 
and can produce high short circuit currents. observe the 

following preventive measures before manipulating any terminal 
block identified in the labelling as «batteries»:

 

ˆ

Disconnect the corresponding protection elements.

 

ˆ

when connecting a battery cabinet to the equipment, re-
spect the cable’s polarity and colour (red-positive; black-
negative) indicated in the manual and in the corresponding 
labelling.

 

ˆ

wear rubber gloves and shoes.

 

ˆ

Use tools with insulated handles.

 

ˆ

Take off watches, rings or other metal objects.

 

ˆ

Do not place metal tools or objects over the batteries.

 

ˆ

never manipulate with your hands or through conducting 
objects, do not short either the battery terminal block of the 
equipment or the own from the batteries.

•  when the equipment and/or battery module has a protection 

through a fuse and it is needed to be replaced, it will always be 
done by another one with the same dimension, type and size.

•  For long periods of disconnection, consider that the equipment 

has to be connected once a month for 10 hours as minimum, in 
order to charge the batteries, so the irreversible degradation of 
itself is avoided. on the other hand, in case of storing an equip-
ment, it will be done in a fresh and dry place, never outdoors.

•  never short the battery terminals as it involves a high risk. it involves 

the detriment of the equipment and batteries.

•  Avoid mechanical efforts and impacts.
•  Do not open or mutilate the battery. Spilled electrolyte is harmful 

and toxic to the skin and eyes.

•  Do not dispose the batteries in a fire and high temperatures. The 

batteries may explode.

•  in case of contact of the acid with parts of the body, wash imme-

diately with plenty water and call urgently the nearest medical 
service.

•  batteries involve a serious risk for the health and for the environ-

ment. Their disposal should be done according to the existing 
laws.

Summary of Contents for KESSUPS 91RT

Page 1: ...UPSseriesKESSUPS91RT 700VA 10kVA Uninterruptible Power Supply User s manual...

Page 2: ...3kVAequipmentsonly 4 3 8 Dry_out terminals drycontactforalarm 0 7to3kVAequipmentsonly 4 3 9 Connectioninparallel 4 3 9 1 Introductiontotheredundancy 4 3 9 2 Installationandparalleloperating 4to10kVAeq...

Page 3: ...amage the goods Precaution symbol Read the paragraph text and take the stated preventive mediums it contents the basic instructionsandfeaturesfortheequipmentsafety Tonotrespect these indications can c...

Page 4: ...UPSdrivestheleakagecurrentof theloaddevices Anisolatedearthcablehastobeinstalledas part of the circuit that supplies the equipment Cross cable section and its features will be same as the power supply...

Page 5: ...art from the implicit stated risks any action that make the modification internal or external of the equipment or just only the simple intervention inside of itself which is not stated in this documen...

Page 6: ...y from the equip ment in another cabinet case or rack with the interlink cables among them Do not modify its length In those equipments requested without batteries their acquisi tion installation and...

Page 7: ...the event of any modification or intervention in the product by the cus tomer s side This is a product for its use in commercial and industrial ap plications so restrictions and additional measures c...

Page 8: ...91RT models from 4 to 6 kVA 3HE from 8 to 10 kVA 5HE Battery module from 0 7 to 3 kVA Battery module from 4 to 6 kVA 3HE from 8 to 10 kVA 5HE Fixing screws Front cover Fixing screws Front cover Fixing...

Page 9: ...put terminals IEC AC outlets LS2 Modelsfrom0 7to2kVAstandard USB COM port RS232 COM port IEC inlet for AC power supply Main earth for battery module Connectorfor remoteON OFF Auxiliary contact connect...

Page 10: ...other module Battery module for equipments from 0 7 to 3 kVA Earth bonding terminal to be connected to the equipment and with other module Battery module for equipments from4 to 6 kVA The connection o...

Page 11: ...rface or SNMP for controlling the equipment via Internet Intranet Models from 4 to 10 kVA allow the parallel connection of a second equipment of the same features for a redundant configuration or to i...

Page 12: ...SNMP adapter The big IT systems based on LANs and WANs that integrate servers with different platforms they have to include an easy way of control ling and management at the manager system disposal Th...

Page 13: ...ing C characteristic for circuit breaker Regardingthesize theywillbeasminimumtothecurrentsstated in the nameplate of each UPS In the nameplate of the equipment there are only printed the nominal curre...

Page 14: ...only 1 metallic piece and bolt to joint the battery module with the equipment on tower format Once the reception is finished it is advisable to pack the UPS and the battery module s again till its com...

Page 15: ...nofthispowerrangeintherackcabinetwhenthemanipula tionsaredonebyhand thebatteryblockhastoberemovedfrom the equipment Proceedasfollowstoremovethebatteryblockorpack basedon one pack for 4 to 6 kVA models...

Page 16: ...r side of the equipment see figure 11 All the instructions relating to connections will detailed later on less those ones regarding the battery connection Therefore this section will only describe the...

Page 17: ...ment vertical There are no supports or stabilizers A A B Fig 7 Vertical tower type assembling 4 2 5 3 Vertical tower type assembling with extended back up time battery module The description of this s...

Page 18: ...8 Model in vertical tower type assembling with extended back up time battery module Regarding the connections of the UPS with the battery module in models up to 6 kVA make the following steps but rea...

Page 19: ...frame of the cabinet by means of the screws B 4 2 5 5 19 rack cabinet assembling with extended back up time battery module This section describes a single equipment with only one battery module see fi...

Page 20: ...seconnectortoconnectitwith anotherbatterymodule Socketforbattery module Wireofbatterymodule Fig 11 Batterymoduleconnectionfor8and10kVAequipments 4 3 Connection Cross cable section used in the power su...

Page 21: ...t the circuit diagram of the particular Backfeed protection for the equipment without bypass line There can be no derivation in the line that goes from the Backfeed protection to the UPS as the safety...

Page 22: ...2 and respect the circuit diagram of the par ticular Backfeedprotection fortheequipmentwithbypassline There can be no derivation in the line that goes from the Backfeed protection to the UPS as the sa...

Page 23: ...the load connected to the respective outlet has to be checked otherwise the protection will be activated and deactivated cyclically and therefore the loads will suffer the consequences For hardwired...

Page 24: ...ting the power supply to the input power block Make sure that all the loads connected to the UPS are only con nectedtotheprotectiveearthbondingterminal Thefactof not restricting the earthing of the lo...

Page 25: ...3 9 2 Installationandparalleloperating 4to10kVA equipmentsonly Communication line COM is a very low voltage circuit of safety Topreservethequality ithastobeinstalledseparate from other lines that have...

Page 26: ...s the difference in the length between the input and output cables of the equipments has to be lower than 10 Input circuit breakers Output circuit breakers Manual bypass UPS nr 1 Input To loads UPS nr...

Page 27: ...other machines or devices through the 5 dry contacts supplied in the terminal strip included in the same card and to each one of them an alarm of the 8 available can be as signed see table 6 Also the...

Page 28: ...of the monitoring software 4 3 12 Considerations before starting up the connected loads It is recommended to charge the batteries for 2 hours as minimum before using the UPS for first time When sup p...

Page 29: ...3 seconds to shut down the inverter The acoustic alarm will beep for 3 sec The equipment will be established on Bypass mode When finishing the previous action there is still voltage at the UPS output...

Page 30: ...hrough the bypass Turn On the output circuit breaker switch of the distribution panel corresponding to the new integrated equipment The complete parallel system will supply output voltage through the...

Page 31: ...tem again 6 Control panel with LCD 6 1 Control panel Fig 20 Control panel view Button Function Description Inverter start up With no AC power supply and battery connected to the equipment press the bu...

Page 32: ...te In ECO mode Blue 65 State In converter mode Blue 71 Warning EPO active Blue 72 Warning On maintain Bypass only models of 4 10 kVA Blue 81 Fault Heatsink over temperature Red 82 Warning Ambient over...

Page 33: ...passwithoutputvoltagescreen Bypass without output voltage The UPS is running on bypass mode without output voltage Fig 25 Bypasswithoutoutputvoltagescreen ECO mode Once the UPS is started up the energ...

Page 34: ...se the UPS could fail Fig 28 Warningscreen Fault When a fault occurs it reveals that some serious problems have happened the UPS will break the output voltage or will transfertobypassandthealarmwillbe...

Page 35: ...ame main screen when pressing the key for more than 1 sec the Structure of the main menu will be displayed see figure 33 Todisplaythedifferentsubmenus pressthekeys or forless than 1 sec considering th...

Page 36: ...see figure 34 Whenpressingthekey formorethan1sec theLCDwillshow the UPS status screen of the main menu structure again Press 1 sec Press o 1 sec Event logger structure menu Main menu structure Press...

Page 37: ...ter When pressing the key for more than 1 sec the LCD panel will display the screen Event log from the main menu structure again Control submenu for 0 7 to 3 kVA models 6 3 4 Measurement submenu When...

Page 38: ...is single or it is parallel and power supply to load s is broken To restore the normal condition the EPO button has to be de activated previously close the circuit again and enter into the ClearEPOsta...

Page 39: ...ctions that could satisfy a special ap plication of the user In case you require any of these special functionalists contact the KESS Support Team to change the standard configuration from fac tory 6...

Page 40: ...as battery has to be charged every 2 months The charging time has to be 12 hours as minimum Under normal conditions the battery lifetime is from 3 to 5 years at20 C Eurobat Ahighertemperaturecancaused...

Page 41: ...ment is too high Check the UPS cooling and ambient temperature of the room 93 Back Feed only 3 kVA On battery mode bypass has voltage Transfer to manual bypass and consult our KESS Support Team Do not...

Page 42: ...9 Troubleshooting guide Warning indications 7 2 3 Troubleshooting guide Other circumstances Circumstance or condition Possible cause Solution Code DescriptionintheLCDpanel 01 Bypass Abnormal Bypass p...

Page 43: ...ered product UPS KESSUPS 91RT series 7 4 Description of the available maintenance and service contracts For the UPS series KESSUPS 91RT additional warranty services are available as an option Also pre...

Page 44: ...62040 3 non linear load Transient recover time of the output voltage with load step 0 100 0 9 Transient recover time of output voltage with load step 20 100 20 6 Frequency With mains present synchron...

Page 45: ...emperature 15 50 C Storage temperature without batteries 20 70 C Operating altitude 1000 m a s l for high altitude correct it according to table 14 Relative humidity 0 95 non condensing Protection deg...

Page 46: ...KESS Power Solutions GmbH Gentzgasse 55 A 1180 Wien T 43 0 1 4704731 0 info kess at www kess at MA_16_03_KESSUPS_91RT_E...

Reviews: