38
Press
> 1 sec.
Press
o
< 1 sec.
Control submenu structure
Main menu structure
Press
< 1 sec.
Press
> 1 sec.
Press
< 1 sec.
(*) Accesible with password only
by the KESS Support-Team
(*) Equipments connected in
parallel only
(*)
(**)
(**)
Control submenu for 4 to 10 kVA models.
Fig. 37.
Control submenu screens.
6.3.5. Control submenu
• when pressing the key for less than 1 sec. from this "Control"
submenu, it is accessed to the control structure (see figure 37 de-
pending on the power rate of the model).
• The acoustic alarm can be activated or deactivated from this
menu. Any new alarm, will activate the own acoustic alarm.
• battery test: it is a control command of the UPS , to make a battery
test of the equipment. it is also possible to do it in the 0,7 to 3kVA
units manually (see section 6.1).
• by means of the "loads segments" menu, the iEC outlets group
stated as "lS1" and/or "lS2"can be activated "on" or deactivated
"off", so the UPS will supply or not voltage to the connected loads
respectively.
Also by means of the winPower software, it is possible to com-
bine other functionality of this menu.
• EPo status cleared: when the EPo button is activated, the UPS
output breaks the supply, either if the configuration is single or it
is parallel and power supply to load/s is broken.
To restore the normal condition, the EPo button has to be de-
activated previously (close the circuit again) and enter into the
"Clear EPo status" submenu to clear the current status of the EPo.
Doing this the alarm of the UPS is cleared and the output voltage
is restored through the bypass (bypass mode). The equipment
recover the start up functionality with its normal procedure. See
figure 38 as an example.
• Error status cleared: when there is a fault in the UPS, the fault and
alarm mode is activated.
To restore the normal status, enter into this menu to clear the
error status. Doing this the alarm of the UPS is cleared and the
output voltage is restored through the bypass (bypass mode). it
is needed to check the cause and cancel it before starting up the
equipment again with its normal procedure.
• The event log clearance of the last events can be done through
this menu. but in lack of this the system logs in the memory the
las 50 events.
• Restore the preset configuration from factory: All values are set
to the preset values from factory. This action can only be done
on bypass mode.
• Shutdown of a single UPS (individual): it is a command to shut-
down the UPS that is running in a parallel system currently and
other equipment of the system will supply the load/s in the par-
allel system.