3-3 Setup Procedure For The Unit (continued)
PRESS
DISPLAY
1 1 1 1
1111 Flashes.
Sample Lockout Code, or enter desired value from
notes or worksheet.
Be sure to record any
changes in the lockout code in case it is
forgotten!
ENT
Last count, unit now in
Run Mode.
Store new LOCKOUT Code. (Sample tryout
below.)
1 1 1 1
LOCK ON
Enter the sample / new value . . . the unit is now
locked!
1 1 1 1
LOCK OFF
Enter the sample / new value. . .the unit is now
unlocked!
The lockout procedure is finished.
MENU ITEM 3
OUTCARD
If the unit is equipped with a serial communications
card, the setup parameters in the following menu
will make The Unit compatible with the master
terminal. The Unit Identification Number (if
multiple units are used), Baud Rate (speed at which
the signal is transmitted) and Parity are selectable.
A 7 bit, ASCII character, with one start bit, one stop
bit and the parity makes up the standard ten bit
transmission character. For more details see
Section 8.
PRESS
DISPLAY
D
DEV TYP
↓
Menu Button
D
LOCKOUT
↓
D
OUTCARD
↓
ENT
UNIT ##
The Unit ID Number identifies the unit for
multi-drop communications. Up to 15 units
may be on one line. A unit will stay off line until
its Unit ID number is received. It will then stay
on line until a carriage return is sent. At which
time, it will send any requested information and
take itself off line. The range of the unit ID
number is 00 to 15
Idea:
A Unit ID number of 00 will keep the unit
on line at all times. No Unit Number
prompt is needed and carriage returns will
not take the unit off line.
Regardless of the above, all requests for
information are replied to at the units earliest
convenience.
PRESS
DISPLAY
CLR
UNIT 00
Clears out existing Unit ID number.
1 4
UNIT 14
Sample Unit ID number.
ENT
PL
↓
SER
↓
Enters new Unit ID number. Note: PL selects
OptoMux® RS422. Make selection and hit enter
to continue.
ENT
BAUDRATE
BAUDRATE flashes then shows current Baud
rate.
Summary of Contents for KEPtrol F/C