Page 10
3-3 Setup Procedure For The Unit (continued)
A+B adds input pulses from A and B
together. A-B subtracts the pulses of input
B from input A. This selection determines the
calculation performed on the incoming data.
Caution: When selecting A-B. Nega
tive rates cannot be displayed only
absolute values will be displayed.
The display will go to all F's when the
net rate goes beyond 7 digits.
PRESS
DISPLAY
D
A-B
↓
Pressing D toggles between selections.
ENT
DEC LOC
Store calculation.
DEC LOC allows the user to choose where
the decimal point will be located when the
net total is displayed. The decimal point is for
display only and does not affect K Factors. Press
the keypad numbers to move the decimal point.
Only one decimal point can be displayed.
Pressing 0 turns off the decimal point.
4
DEC .LOC
As an example, the decimal point will move to the
right of the fourth digit from the right (displays
units and thousandths).
ENT
Last count, unit now
in Run Store new DEC LOC.
Mode.
The Counter portion of The Unit is now set up
and the unit is ready to run.
If you would like to:
a. lockout the unit to prevent unwanted changes
b. setup serial communications
c. setup analog output
Access the menu and refer to the manual's
appropriate section.
MENU ITEM 2
LOCKOUT
This menu item uses a 4 digit security code to
prevent tampering and unwanted changes in the
programming of The Unit. The unit is shipped
from the factory with a lockout code of 1000.
For example: To lock the unit, first make sure it
is in the Run Mode, then press 1 - 0 - 0 - 0. The
words LOCK ON should briefly appear. Once the
unit is locked:
a. You can still toggle between rate and total.
b. Presets A and B can still be accessed but not
changed.
c. The rest of the menu cannot be accessed.
To unlock the unit simply press 1 - 0 - 0 - 0. The
words LOCK OFF will appear briefly. When the
unit is unlocked all menu features are available
for change. To put in a different lockout code
follow this setup procedure.
PRESS
DISPLAY
D
DEV TYP
↓
Menu Button
D
LOCKOUT
↓
ENT
CODE
Enters device routine to program in a 4 digit
Lockout Code. The word CODE appears briefly
then the current Lockout Code number is
displayed.
CLR
0 Flashes.
Clears out existing Lockout Code.
Summary of Contents for KEPtrol F/C
Page 4: ...THIS PAGE IS BLANK...