Page 26
8-10.2 RS232/RS422 Serial Input Codes
DXX(S) (Device and address number followed by
space) activates The Unit that had been
assigned that number. That unit comes on
line and transmits "Device XX:". Unit is
now ready to receive a code or string of
codes separated by a space. A "Carriage
Return" (Enter) code enters the codes and
processing of requests begins.
Note: After device is activated, there must be a
delay to allow "Device # _ _" to be transmitted by
the unit before any new commands are sent to the
unit.
AL
Will transmit Analog Low value.
AH
Will transmit Analog High value.
DC
Will transmit Count.
DR
Will transmit Rate.
KA
Will transmit counter A K Factor.
KA(S)XXX
Will load Counter A K Factor
number.
KB
Will transmit counter B K Factor.
KB(S)XXX
Will load Counter B K Factor
number.
KC
Will transmit rate A K Factor.
KC(S)XXX
Will load Rate A K Factor number.
KD
Will transmit rate B K Factor.
KD(S)XXX
Will load Rate B K Factor number.
PA
Will transmit Preset A value.
PA(S)XXX
Will load Preset A value number.
PB
Will transmit Preset B value.
PB(S)XXX
Will load Preset B value number.
RC
Will reset counter to zero if in "RO"
mode (adding) or set counter to
Preset value if in "SP" mode
(subtracting). Output is reset.
RC(S)XXX
Will set counter to number (no
other change is made).
8-10.3 RS232/RS422 Serial Input Examples
Example A: (S) = Space
Transmit from terminal
Receive from
The Unit
D13(S) [Unit 13 activated] Device #13
PA(S)76546(S)PA(S)
PA 76546 PA
KB(S)1575(S)KB(S)
KB 1575 KB
RC(ENTER)
RC
{Preset A set to 76546, Count "B" K Factor set to
1575, and Counter is reset.}
Example B: (S) = Space
Transmit from terminal
Receive from
The Unit
D7(S) [Unit 7 activated]
Device #7
PA(S)12347(S)PA(S)
PA 12347 PA
RC(S)456789(S)RCC(S)
RC 456789 RC
{Unit Preset set to 12347, Counter set to 456789}