- 9 -
2. Operating KEMPER hygienic flushings, UNIDIRECTIONAL
Menu item: Command
Menu item
[DE]
Description Application Adjustment range
Factory setting
20
[Valve 1]
Switch Valve 1.
Opens the valve and
closes it again on
command
a) Functional check
of the valve
b) Flushing out
stagnant water
(stagnation)
c) Winter draining
On = "OK"
Off = "OK"
Off
21
[Valve 2]
Switch Valve 2.
Opens the valve and
closes it again on
command
a) Functional check
of the valve
b) Flushing out
stagnant water
(stagnation)
c) Winter draining
On = "OK"
Off = "OK"
Off
22
[Factory Setting]
Factory settings.
Sets all settings to
the factory settings.
Problems with the
settings
Press R
is executed
Menu item: Program
Menu item
[DE]
Description Application Adjustment range
Factory setting
30
[OpMode]
Select operating
mode. Choose
between frequent
and seldom flushing
interval
(see Parameter 42)
Select a program by
pressing the buttons
(3)
Frequent = [1]
4-72 hours
Seldom = [2]
48-336 hours
Frequent [1]
Menu item: Parameter
Menu item
[DE]
Description Application Adjustment range
Factory setting
40
[IntSpZ V1]
Interval flushing -
Set Flush Time V1.
-
10 - 999 seconds
180 seconds
41
[IntSpZ V2]
Set interval flushing
- Flush Time V2
.
-
10 - 999 seconds
180 seconds
42
[IntervalZ]
Set interval time -
flushing interval
.
-
[1]:
4 - 72 hours
[2]:
48 - 336 hours
[1]: OP mode
frequent
48 hours
[2]: OP mode seldom
168 hours
43
[NoValve]
Set the number of
valves.
-
1 Valve = [1]
2 Valve = [2]
2 Valve [2]