CP 503/A, CP 505/A,D,K, CP 507/
A,C
Maintenance
Project engineering manual V1.06
69
© KEBA 2021
10.2
Fan
CAUTION!
The fan cover must not be opened during operation.
10.2.1
Fan service life
The typical service life of the fan (L
10
) depends on the ambient temperature
at which the CP 50x/x is used.
Service life typical
at 45 °C
Service life typical
at 50 °C
Service life typical
at 55 °C
Service life typical
at 60 °C
19.3 years (for 16/5
operation)
18 years (for 16/5 op-
eration)
16.8 years (for 16/5
operation)
14.5 years (for 16/5
operation)
9.2 years (for 24/7
operation)
8.6 years (for 24/7
operation)
8 years (for 24/7 op-
eration)
6.9 years (for 24/7
operation)
Information
Since the data is a typical lifetime (L
10
), it is recommended that the fan be
replaced already when 70% the service life has been reached, in order to
avoid an unexpected failure during the running process.
10.2.2
Replacing the fan
The fan is located on the top of the module. To change the fan, the fan cover
on the top of the control must be removed.
For ordering information on the fan cover, see chapter "Accessories".
Caution
Operation without fan is not permitted since this could overheat the module
and destroy it.
ESD
Observe the ESD notes in the chapter
.
Preparation
The following tool is required:
●
Cross screwdriver PH1