P30 x-series
Functions
Configuration manual V4.02
32
© KEBA
4.5.3
Settings
The Modbus TCP feature is disabled by default. If an external meter with a
Modbus TCP network interface was installed in the system, it must be con-
figured in the web interface in advance.
Setting the electric current of the post-meter fuse
The post-meter fuse is designed for a certain electric current level. In order
to calculate the charging current, the electric current of the post-meter fuse
must be set via the DIP switches in the connection panel of the charging sta-
tion. If no external meter is found when the Modbus TCP function is acti-
vated, the charging current is reduced to 10 A.
The setting must be made on the DIP switch DSW1. The following DIP
switches can only set a maximum value that is less than or equal to the elec-
tric current of the post-meter fuse.
DSW1.4 to DSW1.5
Electric current
Figure
25 A
35 A
50 A
63 A
Information
Changes to the DIP switch settings only become effective after a restart of
the charging station!
To restart, press the "Service button" until the first signal tone sounds (ap-
prox. 1 second) or switch off the charging station for a short time via the
line circuit breaker.