cONNecTION Of THe POWer UNIT
4.2.2.3 Cross-section of the supply cable
The conductor cross-section of the supply cable is dependent on the input current, the
cable according to manufacturer's data, as well as the VDE regulations.
4.2.3 connection at Dc voltage supply
- -
U
V
W
PE
T1 T2
++
+U
-U
Legend
1
DC voltage
230V class: 275…373 V
400V-class: 480…746 V
2
Fuses
Type aR
Pay attention to the permissible voltage range !
3
KEB COMBIVERT
G6
Figure 11: Connection at DC voltage supply
4.2.3.1 Terminal block X1B DC connection
X1b
Name
function
cross-section
Tightening torque
++, --
DC
connection
AWG
without
wire-end
ferrule
mm²
with
wire-end
ferrule
0.5…0.6 A
5…6 lb-inch
24...14
0.25…2.5
multi-wire
PE,
Connection
for
protective
earth
Screw M4
for ring crimp connector
1.3 Nm
11 lb inch
Figure 12: Terminal block X1B DC connection
4.2.4 connection of the motor
4.2.4.1 Selection of the motor cable
The correct cabling as well as the motor cable play an important part in case of low power in
connection with long motor line lengths. Ferrite cores and low-capacitance cables (phase/
phase < 65 pF /
m, phase/screen < 120 pF / m) at the output have the following effects:
• Longer motor line lengths
• Less abrasion of the motor gearbox by leakage currents
• Better EMC properties