44
cerTIfIcATION
5
Certification
5.1 ce-Marking
CE marked drive converters are developed and manufactured to comply with the regula-
tions of the Low-Voltage Directive 2006/95/EC and EMC directive (2004/108/EC). The
harmonized standards of the series
were used.
5.2 functional safety
Drive converters with functional safety are marked with the FS logo on the nameplate.
These units are designed and manufactured in accordance with the Machine Directive
(2006/42/EC). The harmonized standard of the series
is used.
5.3 UL Marking
Acceptance according to UL is marked at KEB
drive converter
s
with the adjacent logo on the nameplate.
To be conform according to UL for use on the North American and Canadian Market the
following additionally instructions must be observed (original text of the UL-File):
• “Only for use in WYE 480V/277V supply sources”
• Operator and Control Board Rating of relays (30Vdc.:1A)
• "Maximum Surrounding Air Temperature 45
°
C"
• “Internal Overload Protection Operates prior to reaching the 200% of the Motor Full
Load Current”.
• For 480V rated models:
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 5000 rms Sym-
metrical Amperes, 480 Volts Maximum, see instruction manual for Branch Circuit
Protection details"
and
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 18000 rms
Symmetrical Amperes, 480 Volts Maximum when protected by CC, J or RK5 Class
Fuses", see instruction manual for maximum fuse sizes".
• For 240V rated models:
„Suitable For Use On A Circuit Capable Of Delivering Not More Than 5000 rms Sym-
metrical Amperes, 240 Volts Maximum, see instruction manual for Branch Circuit
Protection details“
and
„Suitable For Use On A Circuit Capable Of Delivering Not More Than 18000 rms
Symmetrical Amperes, 240 Volts Maximum when protected by CC, J or RK5 Class
Fuses“, see instruction manual for maximum fuse sizes“.
• ”Integral solid state short circuit protection does not provide branch circuit protec-
tion. Branch circuit protection must be provided in accordance with the Manufacturer
Instructions, National Electrical Code and any additional local codes”.
continued on the next page