40
cONNecTION Of THe POWer UNIT
NOTICE
Protect motor against voltage peaks !
Drive converters switch at the output with dV/dt ≤ 5kV/µs.
Voltage peaks
that endanger the insulation system at the motor can occur especially
in case of long motor cables (> 15 m).
A motor choke, a dv/dt-filter or sine-wave filter can be used for protec
-
tion of the motor.
4.2.4.7 Terminal block X1B motor connection
X1b
Name
function
cross-section
Tightening torque
U, V, W
Motor connec-
tion
AWG
without
wire-end
ferrule
mm²
with
wire-end
ferrule
0.5…0.6 A
5…6 lb-inch
24...14
0.25...2.5
multi-wire
Figure 13: Terminal block X1B motor connection
4.2.4.8 Wiring of the motor
L1
L2
L3
U
V
W
U
V
W
T1 T2
➃
➄
1 KEB COMBIVERT
2 Apply motor cable, shielding on both sides over a
large surface on the function earth
3 Three-phase motor
4 Temperature monitoring (optional)
=>
„Connection of a temperature detection“
5 Connection via shield plate (if not available, place on
mounting plate)
Figure 14: Wiring of the motor
NOTICE
• Do not lay PTC cable of the motor (also shielded) together with con-
trol cable !
• PTC cable inside the motor cable only permissible with an addition-
ally shielding (double shielding) !