
Installation and Connection
9
ANTRIEBSTECHNIK
2.4.4 Temperature Monitoring
Bridge, when no monitoring occurs.
Thermocontact (NC-contact)
Temperature detector (PTC)
2.5 Connection and Control
To prevent maloperations caused by interference voltage supply observe the following:
•
Use shielded / drilled lines.
•
Install shield on one side of the inverter onto the earth potential.
•
Install control and power cable separately (distance about 10-20cm).
•
Install crossing, if not avoidable, in a right angle.
2.5.1 Terminal
Terminal X1
Pin
Name
Function
Default Function
X1.1
RLA
programmable relay output
X1.2
RLB
A = NO-contact / B = NC-contact /
alarm relay
X1.3
RLC
C = Basis (Out2)
X1.4
I1
programmable digital inputs
fixed frequency 1
X1.5
I2
fixed frequency 2
X1.6
0V
ground
ground for digital I/Os
X1.7
CRF
10 V output
supply voltage for setpoint
potentiometer
X1.8
REF
setpoint input
0...10VDC for analog setpoint input
X1.9
COM
common
ground for analog I/O’s
X1.10
AN-
OUT
analog output
(digital output)
(Out1)
analog output e.g.:
the output frequency (An.14 = 0)
or digital output (An.14 = 7)
X1.11
Uext
15 V
supply voltage for digital I/O’s
X1.12
REV
direction of rotation: reverse
direction of rotation
X1.13
FOR
forward
presetting: forward has priority
X1.14
ST
control release / reset
power modules released; reset
when opened
OH
OH
OH
OH
OH
OH
Summary of Contents for COMBIVERT F4-S/1.2
Page 2: ......
Page 24: ...ru Parameter 24 ...
Page 42: ...uF Parameter 42 ...
Page 54: ...Fr Parameter 54 ...
Page 58: ...An Parameter 58 ...
Page 64: ...di Parameter 64 ...
Page 76: ...In Parameter 76 ...
Page 94: ......
Page 95: ...ANTRIEBSTECHNIK ...