Parameter Tables
78
6.2 oP-Parameter
Size
No. Name
Adr.
(hex)
P E ro Res.
Lower
Limit
Upper
Limit
Default
Value
Unit
oP
0 Frequency Reference
Source
2100
• •
1
0
8
1
oP
1 Frequency Reference
Setting Absolute
2101
•
0,0125 -409,58 409,58
0 Hz
oP
2 Frequency Reference
Setting
2102
•
0,1
-100
100
0
%
oP
3 Rotation Setting
2103
• •
1
0
2
0
oP
4 Minimum Reference
2104
•
0,0125
0 409,58
0 Hz
oP
5 Maximum Reference
2105
•
0,0125
0 409,58
70 Hz
oP
8 Absolute Maximum
Frequency
2108
•
0,0125
0
In. 2 409,58 Hz
oP
11 Acceleration Time
210B
•
0,01
0
300
10
s
oP
12 Deceleration Time
210C
•
0,01
0
300
10
s
oP
22 Step Frequency 1
2116
•
0,0125 -409,58 409,58
5 Hz
oP
23 Step Frequency 2
2117
•
0,0125 -409,58 409,58
50 Hz
oP
24 Step Frequency 3
2118
•
0,0125 -409,58 409,58
70 Hz
oP
25 Step Frequency Mode
2119
•
1
0
3
2