Installation and Connection
10
2.5.2 Digital Inputs
4
5
11 12 13 14
PE
4
6
12 13 14
PE
+
5
2.5.3 Analog Inputs
7
8
9
PE
REF
3...10 k
Ω
Ω
Ω
Ω
/ 0.5 W
8
9
+
-
SPS
PE
REF
0...10V Ri
≈≈≈≈
56 kOhm
Analog inputs that are not used must be connected to the earth reference. To prevent
undefined conditions during external supply, make sure to switch on the supply first
and then the inverter.
2.5.4 Outputs
Analog Output:
0...10V DC when Ri
≥≥≥≥
56 k
Ω
Ω
Ω
Ω
const.
0...1mA DC when Ri
≤≤≤≤
5k
Ω
Ω
Ω
Ω
const.
0 or 10V as digital output (An.14 = 7).
Relay RLA/B/C
Internal Voltage
Supply
External Voltage
Supply
Internal Voltage
Supply
External Voltage
Supply
1
2
3
9 10
+
PE
Summary of Contents for COMBIVERT F4-S/1.2
Page 2: ......
Page 24: ...ru Parameter 24 ...
Page 42: ...uF Parameter 42 ...
Page 54: ...Fr Parameter 54 ...
Page 58: ...An Parameter 58 ...
Page 64: ...di Parameter 64 ...
Page 76: ...In Parameter 76 ...
Page 94: ......
Page 95: ...ANTRIEBSTECHNIK ...