do - Parameter
66
do.0 makes it possible to invert the digital outputs. The parameter is bit coded.
Bit -No.
Decimal
Value
Output
Terminal
0
1
Out 1 (analog Out)
10
1
2
Out 2 (Relay RLA,RLB,RLC)
1 , 2 , 3
For every output that should be inverted, the respective decimal value is adjusted. If
both outputs should be inverted, then the sum of the decimal values (3) is adjusted
These parameters set the output conditions, which are assigned to the outputs Out 1 -
Out 2 with parameters do.9 - do.25:
Value Function of the Output
0
always inactive
1
always active
2
alarm relay
3
alarm relay (not during active Auto-Restart-function)
4
overload-pre-warning (see also LE.32)
5
overtemperature pre-warning inverter
(Warning when the inverter-temperature sensor is triggered,
error after xx sec.)
6
temperature detector (PTC) pre-warning
(warning when the motor-PTC is triggered,
error after the Pn.16 has run).
7
always active
8
stall
9
LA-/LD-Stop
10
dc-braking
11
always active
12
rate of utilization (ru. 7) > rate of utilization level (LE. 8 .. LE.10(15))
13
active current (ru.10) > active current level (LE.16 .. LE.18(23))
14
actual value = set value (ru. 0 = Fcon, rcon; not at noP, LS, error, SSF)
15
accelerate (ru. 0 = FAcc, rAcc, LAS)
16
decelerate (ru. 0 = FdEc, rdEc, LdS)
17
forward (not at noP, LS, error)
18
reverse (not at noP, LS, error)
19
actual direction of rotation = set direction of rotation
20
| actual value | > frequency level (LE. 0 .. LE. 2(7), LE.36)
21
| setpoint | > frequency level (LE. 0 .. LE. 2(7), LE.36)
22
always inactive
23
run signal (ru. 0 <> error)
24
operating signal (modulation active)
To activate the output condition for the respective output the prevailing decimal value
in the parameter "Selection of output condition Out X" is set. The state of the output
condition is displayed in parameter ru.17. Each output condition can be inverted by
setting the respective decimal value in the parameter "Logic of the output conditions
Out X".
Bit-No.
Decimal Value
Output Conditions
0
1
1
1
2
2
There may be several conditions valid for the output. In this case, the sum of the
decimal value must be set.
Output Logic
(do. 0)
Output Condition
1 - 2 (do. 1 - do. 2)
Select Condition
(do. 9 - do.10)
Condition Logic
(do.17 - do.18)